Weil-McLain CF1400-W Burner User Manual


 
Weil-McLain 88 Water and Steam Boilers — Series 2 — For Gas, Light Oil, & Gas/Light Oil-Fired Burners
2 Part No. 550-142-026/0508
Burner dataTable 1
Boiler
Model Number
Burner Input (Forced
Draft) No. 2 Oil
Low Fire Firing Rate
No. 2 Oil
Positive Pressure
in Firebox
Standard
Burner Model
Designation
Becket
Part Number
for Ordering
GPH GPH Inches W.C.
488R 6.90 4.90 0.60 CF1400-W WL 7001
488 7.00 5.00 0.60 CF1400-W WL 7001
588 9.40 6.8 0.60 CF2300A-W WL7101
688 11.80 8.51 0.65 CF2300A-W WL7102
788 14.20 10.41 0.65 CF2300A-W WL7103
888 16.60 8.30 0.65 CF2500A-W WL7201
988R 17.20 11.60 0.65 CF2500A-W WL7202
988 18.80 9.53 0.65 CF2500A-W WL7202
1088R 20.00 9.54 0.65 CF2500A-W WL7301
1088 21.50 11.26 0.65 CF2500-W WL7301
1188 23.50 12.30 0.65 CF2500-W WL7302
1288 26.00 13.00 0.65 CF3500A-W WL7401
1388 28.50 15.00 0.70 CF3500A-W WL7402
Boiler
Model Number
Standard
Combustion Control
Air Tube
Combination
Starting
Head Setting
Approximate Air Settings
Low Fire High Fire
488R Beckett 7505P1515/CC CF66KD 4 39 54
488 Beckett 7505P1515/CC CF66KD 4 39 54
588 Beckett 7505P1515/CC CF66KG 0 34 42
688 Beckett 7505P1515/CC CF66KG 3 41 51
788 Beckett 7505P1515/CC CF66KG 6 43 54
888 Beckett 7505P1515/CC CF66KP 2 25 50
988R Beckett 7505P1515/CC CF66KP 4 28 54
988 Beckett 7505P1515/CC CF66KP 4 27 52
1088R Honeywell RM7840M CF66KP 8 29 59
1088 Honeywell RM7840M CF66KP 8 29 59
1188 Honeywell RM7840M CF66KP 3 29 44
1288 Honeywell RM7840M CF80KM 3 31 63
1388 Honeywell RM7840M CF80KM 6 33 98
Burner specifications and settings