3223
2
GB
TECHNICAL DATA
SPECIFICATIONS
BURNER DIMENSIONS
E1: 10-inch long (254mm) tubes are also available.
BURNER COMPONENTS IDENTIFICATION
Fuel No heavier than # 2 fuel oil
F3 Firing rate - Effective Output 0.50 to 0.95 US GPH - 70,000 to 133,000 BTU/h
F5 Firing rate - Effective Output 0.75 to 1.65 US GPH - 105,000 to 231,000 BTU/h
Voltage (single phase) 120V 60Hz (+ 10% - 15%)
F3 Absorbed electrical power 155 Watts
F5 Absorbed electrical power 175 Watts
Motor (rated) 3250 rpm Run Current 2.2 AMP
Capacitor 12.5 Microfarads
Pump pressure 130 to 200 psig
Primary control RIELLO 530 SE/C
Ignition transformer 8kV 16mA
Model A B C D E F
F3
Inches 8 15/32 9 59/64 6 15/32 3 1/2 6 8 29/32
mm 215 252 164 89 152 226
F5
Inches 9 11/64 10 11/16 7 3/32 3 1/2 6 9 13/32
mm 233 272 180 89 152 239
BURNER COMPONENTS
1 Lockout indicator lamp and reset button
2 Primary control
3 Primary control sub-base
4 Pump pressure regulator
5 Motor
6 Air adjustment and shutter
7 Electronic air shutter assembly
8 Combustion head
9 Semi flange 2 pieces
10 Mounting flange with gasket
11 Supply fuel line port
12 Pump valve (coil)
13 Vacuum gauge port
14 Pressure gauge and bleeder port
15 Return fuel line port
5
1
/
2
”-140mm
7
1
/
2
” - 190 mm
8
15
/
32
” - 215 mm
7
3/
32
” - 180 mm
3
31
/
32
”
101 mm
6
0
°
4
5
°
30
°
D7351
D7352
B
A
EF
E1
C
D
D7304
1
2
3
4
5
6
7
11
8
10
9
12
13
1415