www.desatech.com 11113052-01A
INSTALLATION
Continued
MOUNTING HEATER TO FLOOR
Mounting Base Feet to Heater
1. Lay heater cabinet on its back on a table with
the heater bottom overhanging the table edge.
2. Align holes in base foot with mounting holes
on bottom of cabinet (see Figure 13).
3. Secure base foot to heater using sheet metal
screws.
4. Repeat for other side.
Mounting Base Feet to Floor (Where
required by local code)
1. Remove front cover (see Removing Front
Panel of Heater, page 8).
2. Position heater with base feet in desired loca-
tion. Mark holes for drilling. Remove heater
with base.
3. For carpeted floors, make a small cut with a
sharp knife at marked locations prior to drill-
ing. If mounting base to a wood floor, drill 1/8
inch diameter hole, 3/4 inch deep. (Do not use
anchors in wood floors).
If mounting base to a concrete floor, drill with
1/4 inch diameter concrete drill bit, 1
3
/8 inches
into floor. Insert anchors completely into holes.
4. Reposition heater with base feet over holes.
Secure base to floor with wood screws. See
Figure 13.
Figure 13 - Installing Base Feet
Wood
Screw
Sheet Metal Screw
Base Foot
CONNECTING TO GAS SUPPLY
WARNING: This appliance
requires a 3/8" NPT (National
Pipe Thread) inlet connection to
the pressure regulator.
WARNING: A qualified service
person must connect heater to
gas supply. Follow all local codes.
WARNING: For natural gas,
never connect heater to private
(non-utility) gas wells. This gas is
commonly known as wellhead gas.
IMPORTANT:
For natural gas, check gas line
pressure before connecting heater to gas line. Gas
line pressure must be no greater than 14 inches of
water. If gas line pressure is higher, heater regula-
tor damage could occur.
CAUTION: For propane/LP
gas, never connect heater directly
to the propane/LP supply. This
heater requires an external regu-
lator (not supplied). Install the ex-
ternal regulator between the
heater and propane/LP supply.
For propane/LP gas, the installer must supply an
external regulator. The external regulator will re-
duce incoming gas pressure. You must reduce in-
coming gas pressure to between 11 and 14 inches
of water. If you do not reduce incoming gas pres-
sure, heater regulator damage could occur. Install
the external regulator with the vent pointing down
as shown in Figure 14. Pointing the vent down
protects it from freezing rain or sleet.
Figure 14 - External Regulator With Vent
Pointing Down
External
Regulator
Propane/LP
Supply Tank
Vent
Pointing
Down