Vanguard Heating VGP30B Gas Heater User Manual


 
15
100100
CHECKING
GAS
CONNECTIONS
PRESSURE TESTING GAS SUPPLY PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
1. Disconnect heater and its individual manual shutoff valve from gas supply
piping system. Pressures in excess of 1/2 PSIG will damage heater regulator.
2. Cap off open end of gas pipe where manual shutoff valve was connected.
Continued
IMPORTANT:
Hold pressure regulator with wrench when connecting it to gas piping
and/or fittings.
Pressure
Regulator
Tee Joint
Reducer
Bushing to
1/8" NPT
1/8" NPT
Plug Tap
Test
Gauge
Connection *
Sediment
Trap
Tee Joint
Pipe
Nipple
Cap
Manual
Shutoff
Valve *
Heater
Cabinet
1/2" NPT
Pipe Nipple
Ground Joint
Union
Note:
Burner bracket
not shown for clarity
From
External Regulator
(11" W.C. to 14" W.C. Pressure)
3" Minimum
Figure 13 - Gas Connection
* An A.G.A. design certified manual shutoff valve with 1/8" NPT tap is an acceptable
alternative to test gauge connection. Purchase the optional A.G.A. design certified
manual shutoff valve from your dealer. See Accessories, page 27.
WARNING ICON G001
WARNING
Never use an open flame to check for a leak. Apply a mixture of
liquid soap and water to all joints. Bubbles forming show a leak.
Correct all leaks at once.
CONNECTING
TO GAS
SUPPLY
Continued
WARNING ICON G001
WARNING
Test all gas piping and connections for leaks after installing or
servicing. Correct all leaks at once.
WARNING ICON G001
CAUTION
Make sure external regulator has been installed between propane
supply and heater. See guidelines under
Connecting to Gas Sup-
ply
, page 14.