OUTSIDE AIR SUPPLY (optional)
Depending on your location and home construction, outside air may be necessary for optimal performance.
Metal pipe (solid or flexible) must be used for the outside air installation. PVC pipe is NOT approved and should NEVER
be used.
A wind shield over the termination of the outside air pipe or a 90-degree elbow or bend away from the prevailing winds
MUST be used when an outside air pipe is installed through the side of a building. The outside air termination MUST be
at least 1-foot away from the exhaust system termination.
The outside air pipe on your King/Ashley stove is 1 7/8” OD. The outside air connecting pipe must be at least 1 7/8” ID.
The outside air connection used MUST NOT restrict the amount of air available to your stove. The outside air connecting
pipe must be as short and free of bends as possible, and it must fit over, not inside, the outside air connection to the
stove.
NOTE: Dimensions from the floor to your stoves in-
let/exhaust pipes are approximate and may vary de-
pending on your installation.
FIGURE 9
TYPICAL FRESH AIR TERMINATION
FIGURE 8
EXHAUST/INLET LOCATIONS
SPECIAL MOBILE HOME REQUIREMENTS
WARNING! - DO NOT INSTALL IN A SLEEPING ROOM
CAUTION! - THE STRUCTURAL INTEGRITY OF THE MOBILE HOME FLOOR, WALL, AND CEILING/ROOF
MUST BE MAINTAINED.
In addition to the previously detailed installation requirements, mobile home installations must meet the following
requirements:
The stove must be permanently attached to the floor.
The stove must be electrically grounded to the steel chassis of the mobile home with 8 GA copper wire using a
serrated or star washer to penetrate paint or protective coating to ensure grounding.
Vent must be 3 or 4-inch “PL” Vent and must extend a minimum or 36-inches above the roofline of the mobile home
and must be installed using a UL/ULC listed ceiling fire stop and rain cap.
When moving your mobile home, all exterior venting must be removed while the mobile home is being relocated.
After relocation, all venting must be reinstalled and securely fastened.
Check with your local building officials as other codes may apply.