XT302C DELUXE PROGRAMMABLE HEAT-COOL THERMOSTAT
69-1213—1 (T8624)
Pub. No. 18-HD25D7-5
Table 3. Installer Setup Options for the XT302C (continued).
(continued)
Press Time
▲ or ▼
Press Increase ▲ or Decrease ▼ to change setting
Installer
Factory Setting Other Choices
Actual
Select
Setup Number
Display Description Display Description
Setting
Adaptive
Intelligent
Recovery™
control
13 0 Adaptive Intelligent
Recovery (a
Honeywell trademark)
control is activated
(system starts early so
setpoint is reached by
start of program
period)
1 Conventional recovery
(system starts recovery at
programmed time)
Degree
temperature
display
14 0 Temperature displays
in °F
1 Temperature displays in °C
Clock format 16 0 12-hour clock format 1 24-hour clock format
Extended fan
operation in
heating
a
19 0 No extended fan
operation after the call
for heat ends
1, 2 or 3 1—Fan operation extends
30 seconds after the call
ends.
2—Fan operation extends
60 seconds after the call
ends.
3 —Fan operation extends
90 seconds after the call
ends.
Extended fan
operation in
cooling
20 0 No extended fan
operation after the
call for cool ends
1, 2 or 3 1—Fan operation extends
30 seconds after the call
ends.
2—Fan operation extends
60 seconds after the call
ends.
3 —Fan operation extends
90 seconds after the call
ends.
Outdoor
temperature
display (select
models)
24 0 No outdoor
temperature displays
1 Outdoor temperature
displays. Requires a
TAYSENS100A Outdoor
Sensor.
Comfort-R
Enable
28 0 No fan delay 1 or 2 1—30 seconds
2—15 seconds
Minimum
Deadband
Between
Heating and
Cooling in Auto
Changeover
Mode
30 4 Heating and cooling
setpoints can be set
no closer than 4°F
(2°C)
3 thru 10 Heating and cooling
setpoints can be set no
closer than the chosen
value:
3—3°F (1.5°C)
4—4°F (2°C)
5—5°F (2.5°C)
6—6°F (3°C)
7—7°F (3.5°C)
8—8°F (4°C)
9—9°F (4.5°C)
10—10°F (5°C)
Minimum On
Time (Heat)
32 5 5-minute minimum on
time for compressor
0 thru 15 Minimum number of minutes
(0 thru 15) the compressor
will be on during call for
heat