Trane Upflow/Horizontal Right or Upflow/Horizontal Left Induced Draft Gas Furnace Gas Heater User Manual


 
6 22-1640-06-0702 (EN)
General
Data
1
Central Furnace heating designs are certified by AGA and CSA.
2
For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications,
above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.
3
Based on U.S. government standard tests.
4
The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.
Product Specifications 1
MODEL
TYPE
RATINGS
2
Input BTUH
Capacity BTUH (ICS)
3
AFUE
Temp. rise (Min.-Max.) °F.
BLOWER DRIVE
Diameter - Width (In.)
No. Used
Speeds (No.)
CFM vs. in. w.g.
Motor HP
R.P.M.
Volts / Ph / Hz
COMBUSTION FAN - Type
Drive - No. Speeds
Motor HP - RPM
Volts / Ph / Hz
FLA
FILTER — Furnished?
Type Recommended
Hi Vel. (No.-Size-Thk.)
VENT — Size (in.)
HEAT EXCHANGER
Type -Fired
-Unfired
Gauge (Fired)
ORIFICES — Main
Nat. Gas. Qty. — Drill Size
L.P. Gas Qty. — Drill Size
GAS VALVE
PILOT SAFETY DEVICE
Ty p e
BURNERS — Type
Number
POWER CONN. — V / Ph / Hz
4
Ampacity (In Amps)
Max. Overcurrent Protection (Amps)
PIPE CONN. SIZE (IN.)
DIMENSIONS
Crated (In.)
WEIGHT
Shipping (Lbs.) / Net (Lbs)
TUD040C924K
Upflow / Horizontal
40,000
32,000
80.0
30 - 60
DIRECT
10 x 6
1
4
See Fan Performance Table
1/5
1080
115/1/60
Centrifugal
Direct - 1
1/50 - 3000
115/1/60
1.0
Ye s
High Velocity
1 - 17x25 - 1in.
4 Round
Aluminized Steel - Type I
20
2 — 45
2 — 56
Redundant - Single Stage
Hot Surface Ignition
Multi-port In-shot
2
115/1/60
6.3
15
1/2
H x W x D
41-3/4 x 16-1/2 x 30-1/2
119 / 110
TUD040C930K
Upflow / Horizontal
40,000
32,000
80.0
30 - 60
DIRECT
10 x 6
1
4
See Fan Performance Table
1/3
1075
115/1/60
Centrifugal
Direct - 1
1/50 - 3000
115/1/60
1.0
Ye s
High Velocity
1 - 17x25 - 1in.
4 Round
Aluminized Steel - Type I
20
2 — 45
2 — 56
Redundant - Single Stage
Hot Surface Ignition
Multi-port In-shot
2
115/1/60
6.3
15
1/2
H x W x D
41-3/4 x 16-1/2 x 30-1/2
122 / 113
TUD060C924K
Upflow / Horizontal
60,000
47,000
80.0
35 - 65
DIRECT
10 x 6
1
4
See Fan Performance Table
1/5
1080
115/1/60
Centrifugal
Direct - 1
1/50 - 3000
115/1/60
1.0
Ye s
High Velocity
1 - 17x25 - 1in.
4 Round
Aluminized Steel - Type I
20
3 — 45
3 — 56
Redundant - Single Stage
Hot Surface Ignition
Multi-port In-shot
3
115/1/60
10.4
15
1/2
H x W x D
41-3/4 x 16-1/2 x 30-1/2
124 / 115
TUD060C936K
Upflow / Horizontal
60,000
47,000
80.0
30 - 60
DIRECT
10 x 7
1
4
See Fan Performance Table
1/3
1075
115/1/60
Centrifugal
Direct - 1
1/50 - 3000
115/1/60
1.0
Ye s
High Velocity
1 - 17x25 - 1in.
4 Round
Aluminized Steel - Type I
20
3 — 45
3 — 56
Redundant - Single Stage
Hot Surface Ignition
Multi-port In-shot
3
115/1/60
10.4
15
1/2
H x W x D
41-3/4 x 16-1/2 x 30-1/2
127 / 118