Trane TAM7A0C60H51SB Air Conditioner User Manual


 
Pub. No. 22-1847-03 7
TAM7A0A24 AIRFLOW PERFORMANCE
CONSTANT CFM MODE / CONSTANT TORQUE MODE
OUTDOOR
MULTIPLIER
(TONS)
COOLING
AIRFLOW
SETTING
Airow
Power
EXTERNAL STATIC PRESSURE
HEATING
AIRFLOW
SETTING
Airow
Power
EXTERNAL STATIC PRESSURE
0.1 0.3 0.5 0.7 0.9 0.1 0.3 0.5 0.7 0.9
1.5 tons
360
CFM/ton
CFM
Watts
542 / 652
38 / 59
547 / 559
67 / 71
548 / 407
101 / 78
547 / NA
137 / NA
541 / NA
175 / NA
390
CFM/ton
CFM
Watts
586
46
599
80
600
115
599
153
595
192
380
CFM/ton
CFM
Watts
574 / 679
43 / 65
583 / 593
75 / 78
587 / 464
110 / 87
588 / 167
148 / 94
581 / NA
185 / NA
410
CFM/ton
CFM
Watts
618
53
633
88
636
124
637
163
629
202
400
CFM/ton
CFM
Watts
605 / 705
49 / 71
618 / 626
82 / 85
624 / 513
119 / 96
625 / 325
158 / 101
618 / NA
196 / NA
430
CFM/ton
CFM
Watts
650
59
665
96
669
134
672
174
660
212
420
CFM/ton
CFM
Watts
636 / 731
55 / 78
651 / 658
90 / 93
659 / 556
128 / 105
660 / 406
168 / 112
653 / NA
207 / NA
450
CFM/ton
CFM
Watts
681
66
696
104
703
144
704
185
696
225
2 tons †
360
CFM/ton
CFM
Watts
723 / 809
75 / 101
743 / 746
115 / 118
754 / 666
158 / 133
756 / 563
201 / 144
748 / 428
242 / 153
390
CFM/ton
CFM
Watts
780
94
800
137
809
182
811
227
802
268
380
CFM/ton
CFM
Watts
761 / 843
86 / 113
782 / 784
128 / 131
793 / 710
172 / 146
796 / 617
216 / 159
788 / 500
259 / 168
410
CFM/ton
CFM
Watts
818
106
838
151
848
198
851
244
842
287
400 †
CFM/ton
CFM
Watts
799 / 877
97 / 125
820 / 821
141 / 144
832 / 751
187 / 161
835 / 666
233 / 174
827 / 561
276 / 183
430
CFM/ton
CFM
Watts
856
119
876
167
887
215
889
262
881
307
420
CFM/ton
CFM
Watts
836 / 911
109 / 139
858 / 858
155 / 158
870 / 792
203 / 175
873 /712
250 / 189
866 / 615
294 / 199
450
CFM/ton
CFM
Watts
894
134
913
183
925
233
927
282
920
327
2.5 tons
360
CFM/ton
CFM
Watts
892 / 979
130 / 168
914 / 930
179 / 189
927 / 869
229 / 207
930 / 796
278 / 222
923 / 709
324 / 232
390
CFM/ton
CFM
Watts
964
164
986
218
997
271
1000
322
992
370
380
CFM/ton
CFM
Watts
939 / 1024
149 / 190
962 / 976
201 / 211
974 / 918
253 / 230
978 / 849
304 / 244
971 / 766
351 / 255
410
CFM/ton
CFM
Watts
1013
188
1034
244
1045
299
1049
353
1040
400
400
CFM/ton
CFM
Watts
986 / 1070
170 / 215
1009 / 1023
225 / 236
1022 / 967
279 / 255
1026 / 901
332 / 270
1019 / 821
380 / 280
430
CFM/ton
CFM
Watts
1063
214
1083
273
1095
331
1097
385
1089
434
420
CFM/ton
CFM
Watts
1035 / 1118
194 / 242
1058 / 1072
251 / 264
1071 / 1018
308 / 282
1074 / 953
362 / 297
1066 / 877
411 / 307
450
CFM/ton
CFM
Watts
1114
243
1135
305
1145
365
1145
420
1135
469
3 tons
360
CFM/ton
CFM
Watts
1065 / 1148
209 / 261
1088 / 1102
269 / 282
1101 / 1048
327 / 301
1103 / 985
382 / 315
1095 / 910
431 / 325
390
CFM/ton
CFM
Watts
1160
272
1181
337
1190
397
1189
453
1157
486
380
CFM/ton
CFM
Watts
1126 / 1209
244 / 301
1149 / 1164
307 / 322
1160 / 1111
367 / 341
1161 / 1050
423 / 355
1151 / 978
472 / 364
410
CFM/ton
CFM
Watts
1225
317
1244
384
1249
444
1230
486
1146
477
400
CFM/ton
CFM
Watts
1190 / 1271
285 / 347
1211 / 1227
350 / 368
1220 / 1175
412 / 386
1218 / 1115
467 / 399
1164 / 1046
483 / 408
430
CFM/ton
CFM
Watts
1291
368
1305
434
1298
486
1217
476
1135
468
420
CFM/ton
CFM
Watts
1255 / 1334
331 / 397
1273 / 1289
397 / 418
1278 / 1239
459 / 435
1237 / 1180
483 / 448
1151 / 1113
475 / 455
450
CFM/ton
CFM
Watts
1355
422
1361
485
1285
475
1206
467
1124
460
NOTES:
1. † Factory Setting
2. Status LED will blink once per 100 CFM requested. In torque mode, actual airow may be lower.
3. Torque mode will reduce airow when static is above approximately 0.3"
water column.
4. All heating modes default to Constant CFM
5. Cooling airow values are with wet coil, no lter
NOTE: Minimum auxiliary heating airow is automatically congured by the air handler model and
the auxiliary heater model number. This is not eld adjustable.
Minimum Heating Airow Settings
MODEL NO.
BAYEVAC05BK1A
A
BAYEVAC05LG1A
A
BAYEVAC08BK1A
A
BAYEVAC08LG1A
A
BAYEVAC10BK1A
A
BAYEVAC10LG1A
A
BAYEVAC10LG3AA BAYEVCB15LG3A
A
BAYEVBC15BK1A
A
BAYEVBC20BK1A
A
TAM7A0A24H21S
B
638/713 638/900
675 1
/900
600/713 -- -- --
MINIMUM HEATER AIRFLOW CFM - HEATER MATRI
X
WITHOUT HEAT PUMP / WITH HP
SEE AIR HANDLER NAMEPLATE FOR APPROVED COMBINATIONS
1
Heater not qualified for 208V when installed in horizontal left position without Heat Pump