21
Performance
Data
SSP-PRC002-EN
(System)
Table PD-10 — Gross Heating Capacities (kW)
TWA100A Heat Pump with TWE100A Air Handler At 5649 m
3
/h (SI)
Outdoor Heating Capacity (kW) At Total Power in Kilowatts At
Temperature Indicated Indoor Dry Bulb Temperature Indicated Indoor Dry Bulb Temperature
(°C) 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7
-27.8 6.4 11.6 12.6 13.1 5.5 6.0 6.2 6.5
-25.0 9.8 12.8 13.5 13.9 5.6 6.1 6.3 6.6
-22.2 11.9 13.9 14.4 14.7 5.7 6.2 6.5 6.7
-19.4 13.7 15.1 15.4 15.6 5.8 6.3 6.6 6.9
-16.7 15.3 16.3 16.6 16.7 5.9 6.5 6.7 7.0
-13.9 16.9 17.6 17.8 17.8 6.0 6.6 6.9 7.2
-11.1 18.5 19.0 19.1 19.1 6.2 6.7 7.0 7.4
-8.3 20.2 20.4 20.5 20.4 6.3 6.9 7.2 7.5
-5.6 21.9 22.0 22.0 21.9 6.5 7.0 7.4 7.7
-2.8 23.7 23.7 23.6 23.5 6.6 7.2 7.5 7.9
0.0 25.6 25.4 25.3 25.2 6.8 7.4 7.7 8.1
2.8 27.4 27.2 27.1 27.0 6.9 7.6 7.9 8.3
5.6 29.3 29.1 29.0 28.8 7.1 7.8 8.1 8.5
8.3 31.3 31.0 30.9 30.8 7.3 8.0 8.4 8.8
11.1 33.5 33.1 33.0 32.9 7.5 8.2 8.6 9.0
13.9 35.7 35.3 35.2 35.0 7.7 8.4 8.8 9.2
16.7 38.0 37.6 37.4 37.3 7.9 8.7 9.1 9.5
19.4 40.3 39.9 39.7 39.6 8.1 8.9 9.3 9.8
22.2 42.7 42.3 42.1 41.9 8.4 9.2 9.6 10.0
Correction Factors - Other Airflows
(Table Value x Correction Factor = Value at new airflow)
Airflow 3000 cfm 3675 cfm
5097 m
3
/h 6243 m
3
/h
Heating Capacity x 0.99 x 1.01
Compressor kW x 1.02 x 0.98
Values at ARI Rating Conditions of:
70F (21.1C) and 47/43F (8.3/6.1C)(High Temp.Cond.)
70F (21.1C) and 17/15F (-8.3/-9.4C)(Low Temp. Cond)
Airflow = 3325 cfm (5649 m
3
/h)
Heating Capacity (High Temp.) = 106,000 (31.05)
Heating Capacity (Low Temp.) = 69,000 (20.29)
Compressor Power (High Temp) = 7.61 kW
Compressor Power (Low Temp) = 6.38 kW
Coeff. Of Perf. (High Temp) = 3.30
Coeff. Of Perf. (Low Temp) = 2.4
Outdoor Fan Power = 644 watts
Indoor Fan Power = 1,170 watts
Note:
1. Rated with 25 feet of 1-3/8" suction and 1/2" liquid line.
Table PD-10 — Gross Heating Capacities (MBh)
TWA100A Heat Pump with TWE100A Air Handler At 3325 CFM (I-P)
Outdoor Heating Capacity (Btu/1000) At Total Power in Kilowatts At
Temperature Indicated Indoor Dry Bulb Temperature Indicated Indoor Dry Bulb Temperature
(°F) 60 70 75 80 60 70 75 80
-18 21.9 39.6 43.0 44.8 5.6 7.3 7.9 8.4
-13 33.4 43.6 46.0 47.3 6.2 7.5 8.0 8.5
-8 40.8 47.5 49.2 50.2 6.6 7.6 8.1 8.6
-3 46.7 51.5 52.8 53.4 6.8 7.8 8.2 8.7
2 52.3 55.7 56.5 57.0 7.0 7.9 8.4 8.8
7 57.7 60.1 60.6 60.8 7.2 8.1 8.5 8.9
12 63.2 64.8 65.1 65.1 7.4 8.2 8.6 9.1
17 68.9 69.8 69.9 69.8 7.5 8.4 8.8 9.2
22 74.8 75.1 75.1 74.9 7.7 8.5 9.0 9.4
27 80.9 80.8 80.6 80.3 7.9 8.7 9.1 9.6
32 87.3 86.8 86.5 86.2 8.0 8.9 9.4 9.8
37 93.6 92.9 92.6 92.2 8.2 9.1 9.6 10.1
42 100.2 99.3 98.9 98.5 8.4 9.3 9.8 10.3
47 107.1 106.0 105.6 105.2 8.6 9.5 10.1 10.6
52 114.4 113.2 112.7 112.3 8.8 9.8 10.3 10.9
57 121.9 120.6 120.1 119.7 9.1 10.1 10.6 11.2
62 129.7 128.3 127.8 127.3 9.3 10.4 10.9 11.5
67 137.7 136.2 135.6 135.1 9.6 10.7 11.2 11.9
72 145.9 144.3 143.7 143.2 9.9 11.0 11.6 12.2