Trane GAT2A0C60S51SA Air Conditioner User Manual


 
10 Pub. No. 22-1857-03
Performance
Data
WIRING DATA
GAT2A0B42S31SA
Heater
Model
No.
No.
of
Circuits
240 VOLT 208 VOLT
Capacity
Heater
Amps
per
Circuit
Minimum
Circuit
Ampacity
Maximum
Overload
Protection
Capacity
Heater
Amps
per
Circuit
Minimum
Circuit
Ampacity
Maximum
Overload
Protection
kW BTUH kW BTUH
No Heater - - - 2.7** 3 15 - - 2.7** 3 15
BAYEAAC05++ 1 4.80 16400 20 28 30 3.60 12300 17.3 25 25
BAYEAAC08++ 1 7.68 26200 32 43 45 5.76 19700 27.7 38 40
BAYEAAC10++ 1 9.60 32800 40 53 60 7.20 24600 34.6 47 50
BAYEABC15++
circuit 1 9.60 32800 40 53 60 7.20 24600 34.6 47 50
circuit 2 4.80 16400 20 25 25 3.60 12300 17.3 22 25
BAYEABC20++
circuit 1 9.60 32800 40 53 60 7.20 24600 34.6 53 60
circuit 2 9.60 32800 40 50 50 7.20 24600 34.6 43 45