Trane GAF2A0A36S31SA Air Conditioner User Manual


 
Pub. No. 22-1858-02 9
Performance
Data
GAF2A0A30 AIRFLOW PERFORMANCE TABLE
AIRFLOW PERFORMANCE
GAF2A0A30S21SA
EXTERNAL STATIC
(in w.g)
Speed Taps - 230 VOLTS Speed Taps - 208 VOLTS
3 2 † 1 3 2 1
0 1052 967 932 1024 877 826
0.1 1012 929 898 980 846 800
0.2 963 888 861 934 814 771
0.3 914 849 823 885 777 738
0.4 865 805 784 837 739 703
0.5 816 759 741 788 697 663
0.6 759 698 681 739 640 602
0.7 690 622 592 668 559 515
0.8 589 503 463 559 423 395
0.9 389 336 318 375 285 259
1.0 179 149 119 175 NA NA
NOTES:
1. Values are with wet coil and without filters.
2. Contact your particular filter manufacturer for pressure drop data.
3. Electric heater pressure drop is negligible and is included within the airflow data.
4. † Factory Setting
GAF2A0A30S21SA MINIMUM HEATER AIRFLOW CFM
Heater Minimum Air Speed Tap
Without Heat Pump With Heat Pump
BAYECAA05LG1AA Tap 1 Tap 1
BAYECAA08LG1AA Available soon Available soon
BAYECAA10LG1AA Available soon Available soon
SEE AIR HANDLER NAMEPLATE OR PRODUCT DATA FOR EXCEPTIONS
Note: Heating and cooling speeds are the same, factory
set at Speed Tap #2.