Trane 060E Air Conditioner User Manual


 
22-1752-10 5
General
Data
AHRI Standard Capacity Rating Conditions
AHRI STANDARD 210/240 RATING CONDITIONS
(A) Cooling 80°F DB, 67°F WB air entering indoor coil,
95°F DB air entering outdoor coil.
(B) High Temperature Heating 47°F DB, 43°F WB air entering
outdoor coil, 70°F DB air entering indoor coil.
(C) Low Temperature Heating 17°F DB, 15°F WB air entering
outdoor coil, 70°F DB air entering indoor coil.
(D) Rated indoor airflow for heating is the same as for cooling.
AHRI STANDARD 270 RATING CONDITIONS — (Noise
rating numbers are determined with the unit in cooling opera-
tion.) Standard Noise Rating number is at 95°F outdoor air.
Accessory Description and Usage
Rubber Isolators — 5 rubber donuts to isolate condens-
ing unit from mounting frame or pad. Use on any application
where sound transmission needs to be minimized.
Extreme Conditions Mounting Kit — Bracket kits to secure-
ly mount condensing unit to a frame or pad without removing
any panels. Use in areas with high winds, or on commercial
rooftops, etc.
Low Ambient Cooling — For low ambient cooling below 55°
see Application Guide APP-APG013-EN.