ClimaDry Whole House Dehumidication - ClimateMaster Geothermal Heat Pumps - Rev.: 18 April, 2008B
9
Table 5: Tranquility
20™ ECM Blower Performance Data
Tranquility
20™ (TS) Series with ClimaDry Reheat Option (ECM Motor)
All Tranquility 20™ (TS) units with optional ECM fan motor automatically adjust for the reheat coil. The
small additional pressure drop of the reheat coil causes the ECM motor to slightly increase RPM to
overcome the added pressure drop, and maintain selected CFM up to the maximum ESP.
Residential
Units Only
Model
Max
ESP
(in. wg)
Fan
Motor
(hp)
Tap
Setting
Cooling Mode Dehumid Mode Heating Mode
AUX
CFM
Aux/
Emerg
Mode
Stg 1 Stg 2 Fan Stg 1 Stg 2 Fan Stg 1 Stg 2 Fan
018 0.50 1/2
4 620 750 380 480 590 380 620 750 380 4 750
3 570 700 350 450 550 350 570 700 350 3 700
2 510 620 310 400 480 310 510 620 310 2 650
1 430 530 270 430 530 270 1 650
024 0.50 1/2
4 780 950 470 610 740 470 870 1060 470 4 1060
3 700 850 420 540 660 420 780 950 420 3 950
2 630 770 360 490 600 360 670 820 390 2 820
1 550 670 300 570 690 340 1 690
030 0.50 1/2
4 920 1130 560 720 880 560 1000 1230 560 4 1230
3 820 1000 500 640 780 500 900 1100 500 3 1100
2 740 900 450 580 700 450 800 980 450 2 980
1 660 800 400 700 850 400 1 850
036 0.50 1/2
4 1150 1400 700 900 1090 700 1150 1400 700 4 1400
3 1020 1250 630 800 980 630 1020 1250 630 3 1350
2 890 1080 540 690 840 540 890 1080 540 2 1350
1 740 900 450 750 920 450 1 1350
042 0.50 1/2
4 1290 1580 790 1010 1230 790 1290 1580 790 4 1580
3 1150 1400 700 900 1090 700 1150 1400 700 3 1400
2 1050 1280 640 820 1000 640 1020 1240 640 2 1350
1 920 1120 560 900 1080 560 1 1350
048 0.75 1
4 1420 1730 870 1110 1350 870 1520 1850 865 4 1850
3 1270 1550 780 990 1210 780 1350 1650 775 3 1650
2 1180 1440 720 920 1120 720 1190 1450 720 2 1450
1 1050 1280 640 1020 1250 640 1 1350
060 0.75 1
4 1680 2050 1030 1310 1600 1030 1870 2280 1030 4 2280
3 1500 1830 910 1170 1420 910 1680 2050 910 3 2050
2 1400 1700 850 1090 1330 850 1480 1800 850 2 1800
1 1300 1580 790 1270 1550 790 1 1550
070 0.75 1
4 1830 2230 1100 1420 1740 1100 1830 2230 1100 4 2230
3 1600 1950 980 1250 1520 980 1720 2100 980 3 2100
2 1440 1750 880 1120 1360 880 1670 1950 880 2 1950
1 1200 1580 790 1460 1780 790 1 1780
See ECM control section for details on setting taps.
Airow in CFM with wet coil and clean air lter