12-1-5. Wiring and Setting of Remote Controller Control
(Setup method)
One or multiple indoor units are controlled by
2 remote controllers.
(Max. 2 remote controllers are connectable.)
Terminal block for
remote controller cables
Remote controller
cables (Procured locally)
Indoor unit
Outdoor unit
Remote controller
switch (Sub)
Remote controller
switch (Master)
Sold
separately
213
213
BA
BABA
Sold
separately
Terminal block for
remote controller cables
Indoor unit 1
Outdoor unit
Remote controller
switch (Sub)
Remote controller
switch (Master)
Sold
separately
213
213
BA
BABA
Indoor unit 2
213
BA
Sold
separately
Remote controller
inter-unit wire
(Procured locally)
Inter-unit wiring
between indoor units
(Procured locally)
1 2
1 2
12
Remote controller (Inside of the rear side)
Sub remote
controller
Master remote
controller
DIP switch
2-remote controller control
(Controlled by 2 remote controllers)
This control is to operate 1 or multiple indoor units
are operated by 2 remote controllers.
(Max. 2 remote controllers are connectable.)
When connected 2 remote controllers
operate an indoor unit
<Wireless remote controller>
How to set wireless remote controller to sub
remote controller
Change OFF of Bit [3: Remote controller Sub/Master]
of switch S003 to ON.
[Operation]
1. The operation contents can be changed by Last-
push-priority.
2. Use a timer on either Master remote controller or
Sub remote controller.
<Wired remote controller>
How to set wired remote controller
as sub remote controller
Change DIP switch inside of the rear side of the
remote controller switch from remote controller master
to sub. (In case of RBC-AMT32E)
When connected 2 remote controllers
operate the twin