Toshiba RAV-SP564ATZ-E Air Conditioner User Manual


 
– 60 –
<SP80>
Intermittent power-ON
10 minutes: ON /
5 minutes: OFF
Output [40W or equivalent]
Continuous power-ON
Output [40W or equivalent]
No power
(Normal time) (In defective TO sensor)
TO
15˚C
10˚C
8˚C
18˚C
Power-ON condition TD < 30˚C
Intermittent power-ON
10 minutes: ON /
5 minutes: OFF
Output [40W or equivalent]
Continuous power-ON
Output [40W or equivalent]
No power
TE
18˚C
12˚C
10˚C
20˚C
Power-ON condition TD < 30˚C
REQUIREMENT
In some cases, the sound of power-ON may be
heard. It is not abnormal.
REQUIREMENT
While heating the coil, the power sound may be heard. However it is not a trouble.
5. Short intermittent operation preventive control
1) For 3 to 10 minutes after operation start, in some cases, the compressor does not stop to protect the
compressor even if receiving the THERMO OFF signal from indoor.
However it is not abnormal status. (The operation continuance differs according to the operation status.)
2) When the operation stops by the remote controller, the operation does not continue.
6. Current release control
No. of revolutions of the compressor is controlled by AC current value detected by the outdoor P.C. board so
that the input current of the inverter does not exceed the specified value.
Continuous power-ON
Output [10W or equivalent]
Continuous power-ON
Output [20W or equivalent]
No power
(Normal time)
TE [˚C]
1
6
7
0
Power-ON condition TD < 30˚C
<SP56>
11.0
1
Current [A]
Normal operation
Frequency down
Hold Hold
Model
11 value [A]
SP56 SP80
COOL HEAT COOL HEAT
10.80 13.05 16.0 20.0