Toshiba RAV-SP454AT-E Air Conditioner User Manual


 
– 146 –
Drain pump
Hose band
Drain hose
Float switch
Pipe holder
Heat exchanger support board
(Pipe side)
No.
9
10
Part name
Drain pump,
Float switch,
Drain hose
Evaporator
assembly
Procedure
1. Detachment
1) Perform works in procedures 1. of
2
, 1. of
3
,
1. of
8
.
2) Disconnect lead wires which are connected to
the following connectors of P.C. board assembly.
NOTE)
Unlock locks of the housing to remove the
connectors.
CN34 : float SW (3P: Red)
CN504 : Drain pump lead (2P: White)
3) Loosen hose band, remove cap of the drain
hose, and take off screws while holding drain
pump. Remove them with care that pipes are
not damaged. (Ø4 × 10, 3 pcs)
4) Take off screws while holding metal on float
switch.
Remove them with care so that pipes are not
damaged. (Ø4 × 10, 1 pc)
NOTE)
If the pipes are damaged, refrigerant leak may be caused. Take out them with great care.
2. Attachment
1) Attach ASSY sheeting metal which was removed in procedure 1. 3) of
9
with care that
pipes are not damaged, and then fix it with screws.
2) Insert the drain hose into the inlet of drain pump, and then fix it with hose band. Arrange
handle of the hose band at contrary side of heat exchanger side and at direction remote from
drain pan assembly.
3) Carry out wiring as before, and then perform work of procedure 2. of
8
.
NOTE)
Finally check whether they correctly operate or not.
1. Detachment
1) Recover refrigerant, and then remove refriger-
ant pipes at indoor unit side.
2) Perform works of procedures 1. of
2
, 1. of
3
, 1.
of
8
.
Remove sensors.
3) Take off screws of the pipe holder, and remove
the pipe holder. (Ø4 × 10, 2 pcs)
4) Take off screws of the heat exchanger support
board (Pipe side), and remove the heat
exchanger support board
(Pipe side). (Ø4 × 10, 4 pcs)
5) Take off screws of the heat exchanger support
board (Opposite side) which fixes terminal
block of the evaporator assembly.
4 × 10, 2 pcs)
6) Remove the evaporator assembly.
2. Attachment
1) Fasten the parts as before in order, Evaporator
assembly Pipe holder Set sensors
Drain pan assembly Under panel.
2) Connect the refrigerant pipe as before, and
then perform vacuuming.
Remarks