Toshiba RAV-SP404ATZG-E Air Conditioner User Manual


 
– 143 –
2 screws
TA sensor
Hooking part
E-cover
E-cover
E-cover
E-cover
E-cover
E-cover
ClampClamp
Drain pump
Lead wire:
For only drain pump incorporated model
2 screws
Tie wrap
Tie wrap
Tie wrap
No.
3
4
Part name
E-cover
E-box
Procedure
1. Detachment
1) Perform work 1. of
2
.
2) Take off screws fixing E-cover, and then
remove hooks of the hooking part by lifting up.
4 × 10, 2 pcs)
2. Attachment
1) Hang on E-cover to hooks of the hooking part
so that it does not fall down.
NOTE)
Be sure not to catch TA sensor in the E-cover;
otherwise the equipment cannot operate correctly.
2) Using the screws taken off in procedure 1. 2) of
3
, attach E-cover while holding it with hands
without clearance.
NOTE)
If there is clearance, dust may enter in the electric
parts box.
1. Detachment
1) Perform works 1. of
2
and 1. of
3
.
2) Remove clamps and tie wrap at upper part of
the photo. (Drain pump incorporated model: 3
positions)
(Natural drain model: 2 positions)
3) Take off screws fixing E-box. (Ø4 × 10, 2 pcs)
E-box does not fall down under condition that
screws are taken off.
4) Remove the E-box over sheeting metal which
was fixed with screws.
2. Attachment
1) Insert hooks of E-box into the hooking part of
the main body.
2) Store E-box as before, and then attach it by
using screws taken off in procedure 1. 3) of
4
.
NOTE)
Be sure to fix surely as before the lead wires of
which clamps and tie wrap were taken off.
NOTE)
Check that lead wires of the drain pump do not
reach the fan so that they are not caught in the
fan, and then fix them.
(In case of drain pump incorporated model)
Remarks