Toshiba RAV-SP1404AT8Z-E Air Conditioner User Manual


 
– 29 –
1-2. Outdoor Unit
Model Outdoor unit
RAV-SP
RAV-SP
Power supply
Type
Compressor Motor (kW)
Pole
Refirigerant charged (kg)
Refirigerant control
Standard length (m)
Minmum length (m)
Max. total length (m)
Pipe
Additional refrigerant chrge
under long piping connection
Height
Outdoor lower (m)
difference
Outdoor higher (m)
Outer
Height (mm)
Width (mm)
dimension
Depth (mm)
Appearance
Total weight (kg)
Heat exchanger
Connecting pipe
Gas side (mm)
Liquid side (mm)
Fan
Fan unit Standard air flow (m³/min)
Motor (W)
Sound pressure level
Cooling/Heating
(dB•A)
Sound power level
Cooling/Heating
(dB•A)
Outside air temperature, cooling (°C)
Outside air temperature, Heating (°C)
1104AT8-E 1404AT8-E 1604AT8-E 1104AT7 1404AT7 1604AT7
1104AT8-TR 1404AT8-TR 1604AT8-TR
3 phase 4wired (3N-4pole) 3 phase 4wired (3N-4pole)
380V – 415V 50Hz 380V 60Hz
(Power exclusive to outdoor required.) (Power exclusive to outdoor required.)
Hermetic compressor
3.75 3.75 3.75 3.75 3.75 3.75
444444
3.1 3.1 3.1 3.1 3.1 3.1
Pulse motor valve
7.5 7.5 7.5 7.5 7.5 7.5
333333
75 75 75 75 75 75
40g/m (31m to 75m)
30 30 30 30 30 30
30 30 30 30 30 30
1340 1340 1340 1340 1340 1340
900 900 900 900 900 900
320 320 320 320 320 320
Silky shade (Muncel 1Y8.5-0.5)
95 95 95 95 95 95
Finned tube
15.9 15.9 15.9 15.9 15.9 15.9
9.5 9.5 9.5 9.5 9.5 9.5
Propeller fan
101 103 103 101 103 103
100 + 100 100 + 100 100 + 100 100 + 100 100 + 100 100 + 100
49/50 51/52 51/53 49/50 51/52 51/53
66/67 68/69 68/70 66/67 68/69 68/70
46 to –15°C
15 to –20°C