Systematic diagram of refrigerating cycle
RAV-SM2244 series
Standard
Cooling Overload
Low load
Standard
Heating Overload
Low load
Pressure
(MPa) (kg/cm²g)
Pd Ps Pd Ps
3.14 0.88 32.0 9.0
3.54 1.14 36.1 11.6
1.65 0.65 16.8 6.6
2.60 0.67 26.5 6.8
3.24 1.08 33.1 11.0
2.05 0.31 20.9 3.2
Pipe surface temperature (°C)
Discharge Suction
Indoor heat Outdoor heat
exchanger exchanger
(TD) (TS) (TC) (TE)
84 14 10 37
88 17 16 46
41 7 5 0
73 2 42 2
77 14 52 13
76 –12 34 –11
Compressor
drive revolution
frequency
(rps)
64
62
36
66
36
75
Indoor
fan
HIGH
HIGH
LOW
HIGH
LOW
HIGH
Indoor/Outdoor
temp. conditions
(DB/WB) (°C)
Indoor Outdoor
27/19 35/–
32/24 43/–
18/15.5 –15/–
20/– 7/6
30/– 24/18
15/––10/(70%)
This compressor has a 4-pole motor.
The value when compressor frequency (Hz) is measured by a clamp meter is twice the compressor
revolution number (rps).
This data is cycle data obtained by combining a four-way ceiling cassette simultaneous twin at a target pipe
length. Data will change depending on the mounted pipe length or combination with the indoor unit.
RAV-SM2804 series
Standard
Cooling Overload
Low load
Standard
Heating Overload
Low load
Pressure
(MPa) (kg/cm²g)
Pd Ps Pd Ps
3.15 0.79 32.1 8.1
3.62 1.12 36.9 11.4
1.66 0.64 16.9 6.5
2.85 0.63 29.1 6.4
3.26 1.06 33.3 10.8
2.05 0.29 20.9 3.0
Pipe surface temperature (°C)
Discharge Suction
Indoor heat Outdoor heat
exchanger exchanger
(TD) (TS) (TC) (TE)
87 11 9 41
89 18 16 48
42 6 5 0
80 1 47 2
78 14 53 12
81 –13 33 –12
Compressor
drive revolution
frequency
(rps)
80
64
36
80
36
96
Indoor
fan
HIGH
HIGH
LOW
HIGH
LOW
HIGH
Indoor/Outdoor
temp. conditions
(DB/WB) (°C)
Indoor Outdoor
27/19 35/–
32/24 43/–
18/15.5 –15/–
20/– 7/6
30/– 24/18
15/––10/(70%)
This compressor has a 4-pole motor.
The value when compressor frequency (Hz) is measured by a clamp meter is twice the compressor
revolution number (rps).
This data is cycle data obtained by combining a four-way ceiling cassette simultaneous twin at a target pipe
length. Data will change depending on the mounted pipe length or combination with the indoor unit.