22
J. OIL FILTER:
It is strongly recommended that an oil filter assembly be installed in the oil supply line to the unit. This
filter should have the capacity to trap a 40-50 micron particle.
The filter cartridge should be replaced at least once a year. The filter body should be thoroughly cleaned
before installing a new cartridge.
K. ELECTRICAL WIRIING:
: This appliance must be grounded in accordance with local codes, or in the absence
of local codes, with the National Electrical Code
, ANSI/NFPA 70-1999, or the latest edition.
All wiring must conform to the provisions of local codes or, in the absence of local codes, with the
provisions of the National Electrical Code
, ANSI/NFPA 70-1999, or the latest edition, and this instruction
manual.
This appliance requires 120 VAC, 60 Hz, single-phase power. Refer to Table 10 for typical electrical
current draws of the individual appliance motors, recommended sizes for over-current and short circuit
devices, and minimum recommended field wiring sizes. Electrical service must be brought to the unit from
a circuit breaker, or fused disconnect switch, in accordance with local codes. The disconnecting switch
must be located reasonably close to and within sight of the unit. Care must be taken to ensure correct
polarity when wiring the furnace.
Two-wire service, one “hot” lead (L1) and a common (L2), plus a ground conductor, is required. Connect
power to the appliance control system at the junction box in the burner compartment. (A knockout fitting is
provided on the exterior of the burner compartment for this purpose.) A ground wire must be connected to
the grounding wire in the junction box.
Field wiring of power circuits to the appliance should consist of copper conductors rated for at least
15 amp service with an insulation temperature rating of at least 75°C temperature rise. Depending upon
code requirements, rigid or flexible conduit is recommended, and may be required. Connect the electric
power supply as shown in the wiring diagram located on the inside of the front door.
Typically, control wiring between the appliance and the indoor thermostat, and if used, electronic air
cleaner or humidifier, will be required. Field wiring of control circuits should consist of copper conductors
rated for at least 15 amp service with an insulation temperature rating conforming to Type T wire, 35°C
temperature rise. Depending upon code requirements, rigid or flexible conduit is recommended, and may
be required. Make connections between the thermostat, and electronic air cleaner or humidifier (if used),
and the fan control module, inside the vestibule. Consult the wiring diagram for the appropriate
connection points on the thermostat and the fan control module.
Model
Potential/Frequency/
No. of Phases
(V/Hz/Ph)
Supply/Return
A
ir Blower Full
Load Current
(Amps) @ 115
VAC
Oil Burner
Assembly
Full Load
Current
(Amps) @
115 VAC
Maximum
Time Delay
Type Fuse
or Inverse
Time
Circuit
Breaker
Size
(Amps)
Minimum
Recommended
75 deg. C.
Copper Power
Wiring Size
(AWG)
OL6*A072D48 8.0 PSC 15 12
OL6**072DV5 10.1 ECM 15 12
2.6120/60/1
Table 10: Typical Electrical Requirements