SPX Cooling Technologies 7013F081 - 7013J121 Humidifier User Manual


 
Marley
/
MC Fluid Cooler
/
Engineering Data : Hoisting
12
B
D
C
80°MAX
A
1 Hoisting operations can be dangerous and suitable safety
precautions should be taken to protect personnel and the
equipment being hoisted.
2 All hoisting equipment should be certified and comply with
local and national safety regulations.
NOTE
3 Ensure that slings are of sufficient length so not to impose
bending loads onto the casing—use of spreader bars is
essential.
4 For overhead lifts or where additional safety is required,
add slings beneath the fluid cooler unit.
Model
Lower Module Upper Module
A B
Weight
kg
C D
Weight
kg
7012 1422 1143 435 1600 1143 1320
7013 2337 1143 549 2515 1143 1740
7014 3302 1143 699 3429 1143 2175
7054 1245 2057 1186 3327 2438 3942
7055 3073 2057 1640 1753 2438 5450
7073 2515 2794 1610 2515 2794 3996
7074 1295 2642 2071 3531 2794 4908
7075 2743 2642 2905 5207 2794 6545