SPX Cooling Technologies 7012D081 - 7012H121 Humidifier User Manual


 
Marley
/
MC Fluid Cooler
/
Engineering Data : Schematic
10
NOTE
1 Use this bulletin for preliminary layouts only. Obtain
current drawings from your Marley sales representative.
All table data is per cell.
2 Standard overflow is a 1
1
2" dia. M connection located on
the side of the collection basin. Makeup water connection
may be 1
1
2" dia. M connection located on the side of the
collection basin. Drain is a 2"F connection located on the
side of the collection basin.
Model
Dimensions
Motor
kW
Pump
kW
Operating
Weight
kg
Shipping Weight kg
H C Weight per Cell
Heaviest
Section
7073M081
4174
813
18.6
2.2 6190 4541 29307073N081 22.4
7073P081 29.8
7073M101
4402
1041
18.6
2.2 6769 5074 34637073N101 22.4
7073P101 29.8
7073M121
4613
1270
18.6
2.2 7351 5608 39977073N121 22.4
7073P121 29.8
7074N081
4174
813
22.4
3.7 7855 5619 35497074P081 29.8
7074Q081 37.3
7074N101
4402
1041
22.4
3.7 8598 6299 42297074P101 29.8
7074Q101 37.3
7074N121
4613
1270
22.4
3.7 9337 6977 49077074P121 29.8
7074Q121 37.3
7075Q081
4174
813
18.6 x 2
5.6 10986 7674 47697075R081 22.4 x 2
7075T081 29.8 x 2
7075Q101
4402
1041
18.6 x 2
5.6 11927 8615 57107075R101 22.4 x 2
7075T101 29.8 x 2
7075Q121
4613
1270
18.6 x 2
5.6 12852 9451 65467075R121 22.4 x 2
7075T121 29.8 x 2