Soleus Air KY-320 Air Conditioner User Manual


 
18
LCDI POWER CORD AND PLUG
This air conditioner is equipped with an LCDI (Leakage Current Detection and Interruption) power cord and plug
as required by US National Electric Code 440.65. This cord consists of a length of shielded flexible cord with no
termination on the load side and a LCDI attachment plug on the line side.
The LCDI power cord and plug will remove the supply source via electrical disconnect (circuit trip) if the nominal
current leakage between the cord shield and either load conductor exceeds a predetermined value. The cord will
remain de-energized until the devise has been manually reset. This is intended to reduce the risk of a fire in the
power cord or combustible materials nearby. The cord shields are not grounded and they must be considered a
shock hazards if exposed. The cord shield must not be connected to ground or to any exposed metal.
The test and reset buttons on the LCDI Plug are used to check if the plug is functioning properly. To test:
1. Plug power cord into wall outlet
2. Press TEST Button, circuit should trip, cutting power to the air conditioner
3. Press RESET button for use
If a test is performed and the indicator light remains ON, current leakage has been detected. Do not use the air
conditioner or attempt to reset the LCDI Plug. Contact Soleus Air Customer Service for troubleshooting recom-
mendations.
WARNING:
1.DO NOT press TEST button while the air conditioner is operating.
2.The TEST and RESET buttons should not be used as
ON and OFF switches.
3.The cord and plug are not intended to offer protection to externally connected loads or supply circuits.
The cord and plug are intended for indoor use only.