Sierra Monitor Corporation 3100 Smoke Alarm User Manual


 
Model 3100 Series Flame Detectors
Specifications
Sensitivity: 1 ft. sq. Pan fire on axis ~ 80 feet within 5 seconds (using standard fuel)
Switch selectable form 20 to 80 feet to a 1 sq. ft. kerosene fire
Field of View: 120 degree cone
Responsivity: UV - 180 to 260 nm, IR - 0.715 to 3.5 microns, Visible - 480 to 560 nm
Input voltage: 15 to 32 volts, typically 24 volts
Current draw: @24 Volts DC: 72 mA normal mode, 82 mA alarm mode
Temperature range:
Operating: -40°F to 185°F (-40°C to 85°C)
Storage: -67°F to 230°F (-55°C to 110°C)
LEDs: Display switch settings, fault type, fire and verified fire information
Relays:
Model 3100-01: Fire and Fault Relays
Fire Relay: 0.5 amp ~ 120 VAC, 1.0 amp @ 24 VDC resistive, normally open and
normally closed contacts, latching or fire-following modes
Fault Relay: 0.5 amp ~ 120 VAC, 1.0 amp ~ 24 VDC resistive, normally open,
common and normally closed contacts
Enhanced Relay Fire, Fault, Verify and Aux Relays
Models: Verify Relay: 0.5 amp ~ 120 VAC, 1.0 amp ~ 24 VDC resistive, normally open and
normally closed contacts are available. May be operated in either a latching or fire
following mode.
Aux Relay: 0.5 amp ~ 120 VAC, 1.0 amp ~ 24 VDC resistive, normally open and
normally closed contacts are available. Normally used to indicate a Lens Check Fault.
Enclosure: Copper-free Cast Aluminum with epoxy finish
Hazardous area
classification: NEMA 4X Enclosure rating, Explosion Proof
Class I, Div. 1 and 2, Groups B, C, D, Class II, Div. 1 and 2, Groups E, F, G, Class III
Dimensions: 5.4 x 4.8 x 3.7 inches (13.7 x 12.2 x 9.4 cm)
Weight: 3 lbs (1.3 Kg)
Approvals: FM Approved, CSFM: 7210-1608:100
Ordering Information
Model Verified Alarm Aux. Relay Standard Alarm and Trouble Output
3100-01 N/A N/A
These devices have both normally open and
normally closed relay contacts.
3100-02 Open Contacts Closed Contacts
3100-03 Closed Contacts Open Contacts
3100-04 Open Contacts Open Contacts
3100-05 Closed Contacts Closed Contacts
3100-06 20mA N/A Normal 4 mA alarm 12 mA Trouble 0 mA
© 2006 by Sierra Monitor Corporation Rev. B2-06/24/06
esnopseReriFdnamralAeslaF
detaludomnudnadetaludomhtobetarelototytilibasrotcetedehtswohselbatsihT"
lla(e
cruosmralaeslafehtfoecneserpehtnierifatcetedotllitsdnailumitsmralaeslaf
)teef6taerifnaplohoclaretemaid""57.1adesustseterif
ecruoSsmralAeslaFecnatsiDdetaludomnUdetaludoM
ttaW0231retaeHcirtcelEevitsiseRteeF6esnopseRoNesnopseRoN
sbluBttaW04)2(sthgiLtnecseroulFteeF6esnopseRoNesnopseRoN
ttaW005thgiLnegolaHteeF01esnopseRoNes
nopseRoN
ttaW001thgiLtnecsednacnIteeF6esnopseRoNesnopseRoN
ttaW05redleWcrAteeF52esnopseRoNesnopseRoN
Sierra Monitor Corporation 1991 Tarob Ct. Milpitas, CA 95035 (408) 262-6611 800-727-4377 FAX: (408) 262-9042