Shure 8000 Heat Pump User Manual


 
Improper duty cycle and/or rapid start & stop conditions may
cause the internal thermal breaker (if equipped) to trip, or can
result in premature motor failure due to excessive heat. Refer to
the pumps Product Data Sheet.
The pump should be on a dedicated (individual) circuit,
controlled with a double pole switch (UL/C-UL certified) rated at or
above the fuse ampere indicated by the pump motor label.
Depending on distance of the power source from the pump and
ampere load on the circuit, wire may need to be heavier than
indicated by the chart.
CAUTION: All 115 VAC and 230 VAC pump motors and systems,
MUST be ground per local and state electrical codes.
For the pump to meet UL/C-UL requirements the circuit MUST be
protected with a slow-blow fuse (UL/C-UL certified) or equivalent
circuit breaker as indicated on the motor label. Use an approved
wire of the size specified or heavier.
VOLTAGE MODEL FUSE (amp) WIRE LEADS WIRE SIZE
12 DC 800X-X4X-XXX 15.0
8005-X5X-XXX 2.5
24 DC 8005-X9X-XXX RED (positive +)
#
14 AWG [2.5 Mm
2
]
800X-X5X-XXX 10.0 BLACK (negative -) (or heavier)
36 DC 800X-X8X-XXX 5.0
8005-X5X-XXX 1.5
800X-X1X-XXX 1.25 BLACK (common/hot)
115 AC 800X-X2X-XXX WHITE (neutral)
800X-X3X-XXX 1.0 GREEN (ground)
#
18 AWG
800X-X6X-XX C-UL / TEW 1015
800X-X0X-XXX 0.8 BROWN (common/hot) (or heavier)
230 AC 809X-X0X-XX BLUE (neutral) [1 Mm
2
]
800X-X9X-XXX 0.5 GRN/YELL (ground)
809X-X1X-XX
VDE requires a fuse (slow blow) or equivalent circuit breaker.
CAUTION: Circuit protection is dependent on the individual
application requirements. Failure to provide proper overload /