Sears 1F86-382 Thermostat User Manual


 
OPERATION
Before you begin using your thermostat, you should be familiar
with its features and with the display and the location and
operation of the thermostat buttons. Your thermostat consists of
two parts: the thermostat cover and the base. To remove the
cover, pull itstraight out from the base. To replace the cover, line
up the cover with the base and press until the cover snaps onto
the base.
The Thermostat Buttons and Switches
(see fig. 8)
Q Raises temperature setting.
Q Lowers temperature setting.
Q FAN switch (ON, AUTO).
Q SYSTEM switch (COOL, OFF, HEAT).
The Display
Flame icon is when the SYSTEM switch is in
(_) displayed
the HEAT position. Snowflake icon (%)is displayed (non-
flashing) when the SYSTEM switch is in the COOL posi-
tion. Snowflake is displayed (flashing) if the thermostat is
in lockout mode to prevent the compressor from cycling
too quickly.
Displays current temperature.
Q Displays "FILTER" when the has for the
system
run se-
lected filter time period as a reminder to change or clean
your air filter.
Q Displays set is blank when SYS-
point temperature (this
TEM switch is in the OFF position).
Q Displays "BATTERY" and "LO" in the current
temperature
location when the 2 "AA" batteries are low and should be
replaced.
©
®
FAN SYSTEM
CZ) CCD
f ....
w_lwt F Iwlwtl
OOI
Figure 8. Thermostat display, buttons, and switches
I rn L-u-rl
CONFIGURATION MENU
The configuration menu allows you to set certain thermostat
operating characteristics to your system or personal require-
ments.
Move SYSTEM switch to the OFF position, then press (_ and
(_ at the same time to enter the configuration menu. The
display witt show the first item in the configuration menu.
The configuration menu chart below summarizes the configura-
tion options. An explanation of each option follows.
Press (_ and (_ to change to the next menu item. To exit the
menu, move the SYSTEM switch to HEAT or COOL. If no keys
are pressed within fifteen minutes, the thermostat witt exit the
configuration menu.
Configuration Menu
Step PressButton(s) Displayed(Factory Default) Press (_ or (_) to select: COMMENTS
1 Set SYSTEM SYSTEMswitchmustbeOFFto configurethermostat
switch to OFF options
2 (_) and (_) _) SL Select FA or SL (Fast or Slow) heating cycle rate
(FA)
d-L OFF SelectdisplaybacklightOFFor ON
3 (_ and (_) (ON)
4 Q andQ FILTER 0 to 1950 hours SelectFilterreplacementruntime
(000) (in 50 hour increments)
LOC ON SelectCompressorlockoutOFForON
5 (_ and (_) (OFF)
6 (_ and (_) 0 HI 4 LO to Selecttemperaturedisplayadjustmenthigherorlower
(0) 4 HI
7 (_Dand (_ (F) C Selecttemperaturedisplayto For C
8 Set SYSTEM Returnstonormaloperation
switch to HEAT
or COOL
* Press C) and _ to advance to next item