Schneider Electric ACECFR40200SE Fan User Manual


 
EcoBreeze System Installation18
6. Locate the insulation strips packed in the ship-loose kit.
7. Remove the backing from the insulation and apply the insulation around the air transition
ducts.
8. Open the damper on the supply air transition.
Water supply connection
NOTE: There are two water supply inlets on the EcoBreeze Frame. Use separate sources if
possible to provide a redundant water supply.
Sand filtration connections are provided if further filtration of the water supply is required. Sand
filtration systems can be acquired from a third-party vendor.
NOTICE
DAMAGE TO EQUIPMENT
Install adequate freeze protection (not supplied) on all external water piping.
Freeze protection (which may consist of any combination of insulation and electric
heat-tracing) must be correctly applied based on local climatic conditions and best
practices.
Failure to follow these instructions can result in equipment damage.