Sanyo XMHX1252 Air Conditioner User Manual


 
14
Common solenoid valve kit
Multiple indoor units under group control can utilize a solenoid valve kit in common.
Categories of connected indoor unit capacities are determined by the solenoid valve kit.
Table 1-17 Refrigerant Charge Amount at Shipment (for outdoor unit)
DC
CHDZ09053 CHDZ14053
CHDZR09053 CHDZR14053
(oz)
416 416
1-9. System Limitations
Table 1-18 System Limitations
Max. No. allowable connected outdoor units 2
Max. capacity allowable connected outdoor units
307,100 BTU/h (32 hp, 90 kw)
Max. connectable indoor units 40
*1
Max. allowable indoor/outdoor capacity ratio 50 – 130 %
Type of solenoid valve kit Total capacity of indoor units (BTU/h)
160 19.000
<
Total capacity
<
54.600
56 7.500
<
Total capacity
<
19.000
*1: In the case of 20 hp (type 191.100 BTU/h) or smaller units, the number is limited by the total capacity of the connected indoor units.
1-10. Installation Standards
Relationship between A/C units and refrigerant tubing
Outdoor unit Outdoor unit Indoor unit
Suction tube
Discharge tube
Liquid tube
Balance tube
Suction tube
Discharge tube
Liquid tube
Gas tube
Liquid
tube
4-tube layout 3-tube layout 2-tube layout
Solenoid
valve kit
Indoor unit
Room
Hallway
Indoor unit
Room
Indoor unit
Room
Hallway
Indoor unit
Room
Solenoid
valve kit
Solenoid
valve kit
Install the solenoid valve kit 98 ft. or less from the indoor unit.
In quiet locations such as hospitals, libraries, and hotel rooms, the refrigerant noise may be somewhat notice-
able. It is recommended that the solenoid valve kit be installed inside the corridor ceiling, at a location outside
the room.
YES
NO
If the capacity range is exceeded, use 2 solenoid valves connected in parallel.