5. Outdoor unit maintenance remote control
5-5. Monitoring the Outdoor Unit Alarm History: Display of Outdoor Unit Alarm History
* Displays outdoor unit alarms only. Does not display indoor unit alarms.
* Check the indoor unit alarm histories separately using the indoor unit remote
controllers or other control device.
<Operating procedure>
(1) Press and hold the
button and button simultaneously for 4 seconds or longer
to change to outdoor unit alarm history mode.
During the alarm history display, Service Check is lit.
The display and operations are the same as the monitoring of the alarm device
history that is performed using the unit remote controller. However, the outdoor unit
address appears instead of the unit No.
(2) Press the button and select the outdoor unit for alarm history monitoring.
(3) Use the temperature setting and buttons to select the item code for the alarm history.
The display shows the address of the selected outdoor unit, the item code, and the alarm history (alarm data).
The outdoor unit address is displayed as system XX-YY.
System XX = Outdoor unit system address
YY = Outdoor unit sub-bus address
The item code is displayed as 01 08. 01 indicates the most recent alarm.
The alarm history is indicated by the alarm code. (If there have been no alarm codes, is displayed.)
(4) To clear the alarm history, press the button. (The outdoor unit alarm history will be cleared.)
(5) To end, press the button. The display returns to the normal remote controller display.
5-6. Setting Modes: Setting the Outdoor Unit EEPROM
Setting mode 1
<Operating procedure>
(1) Press and hold the button and button simultaneously for 4 sec-
onds or longer.
(2) Use the temperature setting and buttons to change the item code.
The item codes and setting data are shown in the table on the next
page.
(3) Use the timer time and buttons to change the setting data.
To confirm the changed setting data, press the button.
(At this time, Setting stops blinking and remains lit.)
(4) During this mode, Setting is displayed, blinking. The outdoor unit
address display section displays ALL, the item code and number (DN
value in the table), and the setting data (6 digits).
(The setting data is displayed in 6 digits. The display changes between
the first 3 digits (Fig.
A
) and the last 3 digits (Fig.
B
).
When the first 3 digits are displayed, the top point of the colon is lit.)
(5) To end the setting mode, press the button.
(3)
(1)
(4)
(2)
(5)
are displayed alternately.
Display of first 3 digits
A
B
Display of last 3 digits
and
(Example shows display of 000 001.)
A
B
(3)
(1)
(2)
(5)