Sanyo SPW-CR605GXH8B Air Conditioner User Manual


 
11
UK Conditions: Cooling Indoor 23˚C DB 50% RH Outdoor 30˚C Heating Indoor 20˚C Outdoor 0˚C
Rating Conditions: Cooling Indoor 27˚C DB 19˚C WB Outdoor 35˚C DB 24˚C WB Heating Indoor 20˚C DB Outdoor 7˚C DB 6˚C WB
12
UK Conditions: Cooling Indoor 23˚C DB 50% RH Outdoor 30˚C Heating Indoor 20˚C Outdoor 0˚C
Rating Conditions: Cooling Indoor 27˚C DB 19˚C WB Outdoor 35˚C DB 24˚C WB Heating Indoor 20˚C DB Outdoor 7˚C DB 6˚C WB
ECOi 3 Way Heat Recovery VRF Inverter Systems
Dimensions ECOi 2 Way and 3 Way (8-16 HP)
Industry’s smallest changeover boxes - fewer locating
problems
The SANYO solenoid valve kit is only 147mm high (without the
removable bracket) and takes its power from the indoor unit,
saving the cost of an additional supply.
• No additional power supply required
• Single mounting x point
• 2 sizes avaliable (up to 5.6kW and 7.5 to 16kW)
ATK-RZP56BG and ATK-RZP160BG
Solenoid Valve Kit
HP (Combined systems)
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48
Model
C0705DZH8 C0905DZH8 C1155DZH8 C1305DZH8 C1405DZH8 8 C0705DZH8
10 C0905DZH8 10 C0905DZH8 10 C0905DZH8 10 C0905DZH8 12 C1155DZH8 14 C1305DZH8 16 C1405DZH8 10 C0905DZH8 10 C0905DZH8 10 C0905DZH8 10 C0905DZH8 10 C0905DZH8 12 C1155DZH8 14 C1305DZH8 16 C1405DZH8
10 C0905DZH8 10 C0905DZH8 12 C1155DZH8 14 C1305DZH8 16 C1405DZH8 16 C1405DZH8 16 C1405DZH8 16 C1405DZH8 10 C0905DZH8 10 C0905DZH8 12 C1155DZH8 14 C1305DZH8 16 C1405DZH8 16 C1405DZH8 16 C1405DZH8 16 C1405DZH8
14 C1305DZH8 16 C1405DZH8 16 C1405DZH8 16 C1405DZH8 16 C1405DZH8 16 C1405DZH8 16 C1405DZH8 16 C1405DZH8
Power supply
380/400/415V - 3phase/50Hz
Cooling capacity kW
22.40 28.00 33.50 40.00 45.00 50.40 56.00 61.50 68.00 73.00 78.50 85.00 90.00 96.00 101.00 107.00 113.00 118.00 124.00 130.00 135.00
Heating capacity kW
25.00 31.50 37.50 45.00 50.00 56.50 63.00 69.00 76.50 81.50 87.50 95.00 100.00 108.00 113.00 119.00 127.00 132.00 138.00 145.00 150.00
EER Cooling kW
3.78 3.45 3.41 3.45 3.38 3.57 3.46 3.44 3.45 3.41 3.40 3.41 3.38 3.45 3.41 3.42 3.42 3.40 3.41 3.40 3.38
COP Heating kW
4.09 3.95 3.81 3.91 3.79 4.01 3.96 3.88 3.92 3.84 3.80 3.85 3.79 3.93 3.88 3.84 3.88 3.84 3.81 3.83 3.79
Electric ratings
Cooling
Running amperes A
10.0/9.5/9.2 13.7/13.0/12.6 16.6/15.7/15.2 20.0/19.0/18.3 23.0/21.8/21.0 23.8/22.6/21.8 27.3/26.0/25.0 30.2/28.7/27.7 33.6/31.9/30.8 36.5/34.7/33.5 39.4/37.5/36.1 43.0/40.8/39.4 45.9/43.6/42.1 47.5/45.1/43.5 50.5/48.0/46.3 53.0/51.0/49.0 57.0/54.0/52.0 60.0/57.0/55.0 63.0/60.0/58.0 66.0/63.0/60.0 69.0/65.0/63.0
Power input kW
5.93 8.12 9.82 11.59 13.31 14.10 16.20 17.90 19.70 21.40 23.10 24.90 26.60 27.80 29.60 31.30 33.00 34.70 36.40 38.20 39.90
Heating
Running amperes A
10.3/9.8/9.4 13.5/12.8/12.3 16.6/15.8/15.2 19.9/18.9/18.2 22.8/21.6/20.9 23.9/22.6/21.8 26.8/25.5/24.6 30.0/28.5/27.5 33.3/31.6/30.5 36.2/34.4/33.1 39.3/37.3/36.0 42.6/40.5/39.0 45.6/43.3/41.7 46.9/44.6/43.0 49.7/47.2/45.5 53.0/50.0/48.0 56.0/54.0/52.0 59.0/56.0/54.0 63.0/59.0/57.0 65.0/62.0/60.0 68.0/65.0/63.0
Power input kW
6.11 7.97 9.84 11.51 13.19 14.10 15.90 17.80 19.50 21.20 23.30 24.70 26.40 27.50 29.10 31.00 32.70 34.40 36.20 37.90 39.60
Recommended fuse sizes (motor rated)
32 40 32x2
1x40
1x32
2x40
2x32
1x40
1x32
2x40
3x40
Dimensions (H/W/D) mm
1,887x890x890 (+60) 1,887x1,880x890 (+60) 1,887x1,880x890 (+60) 1887x2870x890 (+60)
Net weight kg
290 340 580 630 680 920 970 1020
Airow m
3
/min
150 160 180 200 220 150+160 160+160 160+180 160+200 160+220 180+220 200+220 220+220 160+160+200 160+160+220 160+180+220 160+200+220 160+220+220 180+220+220 200+220+220 220+220+220
Piping connection
Gas
Inches (mm)
3/4 (19.05) 7/8 (22.22) 1 1/8 (28.58) 1 3/8 (34.92) 1 5/8 (41.27)
Discharge
5/8 (15.88) 3/4 (19.05) 7/8 (22.22) 1 1/8 (28.58) 1 3/8 (34.92)
Liquid
3/8 (9.52) 1/2 (12.7) 5/8 (15.88) 3/4 (19.05)
Balance
3/8 (9.52)
Operating sound normal mode
dB(A)
54.5 55.0 56.0 60.0 61.0 57.8 58.0 58.5 57.8 60.1 60.4 61.0 61.5 60.8 61.3 61.5 62.0 62.4 62.6 63.0 63.3
Operating sound quiet mode
51.5 52.0 53.0 57.0 58.0 54.8 55.0 55.5 54.8 57.1 57.4 58.0 58.5 57.8 58.3 58.5 59.0 59.4 59.6 60.0 60.3
Ambient temperature
operating range
Cooling
-10°C DB +43°C DB
Heating
-20°C DB +15°C DB
Maximum number of indoor units
13 16 19 23 26 29 33 36 40
* Condenser actual pipe connections may vary from above pipe connections shown, please refer to technical manuals for full details.
* Please refer to tube sizing charts for pipe selections and pipe length parameters.