Sanyo SAP-CRV93EH Air Conditioner User Manual


 
40
If self-diagnostics function fails to operate
<Checking the indoor and outdoor units>
Checking the indoor unit
Checking the outdoor unit
Checking serial communications
Check the indoor unit.
Is the fuse blown?
ControlNo. Check items (unit operation)
Replace the controller.
Replace the circuit
board or the fuse.
No indicators illuminate and the
indoor fan does not rotate.
Check the power voltage.
Use the remote controller to operate the
unit in “TEST run” mode. To determine
whether the mode is currently in “TEST run”
mode, check the 3 indicator lamps on the
unit. If all 3 are blinking, the current mode is
“TEST run.”
If there are no problems with the above, then check the outdoor unit.
For the “Test run” procedure, refer to 7.4 “How to Test Run the Air Conditioner.”
1
The rated voltage must be present between inter-unit cables 1 and 2.
Connect a 5 k resistor between inter-unit cables 2 and 4. When the
voltage at both ends is measured, approximately 12–15 V DC must
be output and the multimeter pointer must bounce once every 8
seconds.
Or instead of measuring the voltage, you can insert an LED jig and
check that the LED flickers once every 8 seconds.
ControlNo. Check items (unit operation)
Short-circuit terminals 2 and 4 on
the indoor unit terminal base.
Initial self-
diagnostics
Probable location of malfunction
Short-circuit terminals 2 and 4 on
the indoor unit terminal base.
Apply the rated voltage between outdoor
unit terminals 1 and 2.
If there are no problems with the above, then check the indoor unit.
Turn the power OFF before performing short circuiting procedures.
Refer to the previous pages when performing system self-diagnostics.
So that the check can be made quickly, indicators blink at first communication after power ON.
Before performing the above checks, perform “TEST run” operation, and check that the rated voltage is output to terminals 1 and 2 on
the outdoor unit. If it is not output, there is a failure related to the indoor unit power.
1 • The control panel LED (red) must illuminate.
Short-circuit the outdoor unit COM terminal
to the T-RUN terminal.
2 • The compressor, fan motor, and 4-way valve must all turn ON.
Normal
Blown
Control 1
No change Indoor unit circuit board failure
Outdoor unit circuit board failure
Failure (open circuit, contact failure, etc.)
in the inter-unit wiring
Outdoor unit circuit board failure
Change: (1) and (3) illuminate,
and (2) blinks.
(1) illuminates
Change: (1) and (3) illuminate,
and (3) blinks.
Change: (1) and (3) illuminate,
and (2) blinks.
Change: (1) illuminates
(1) and (3) illuminate,
and blinks.
Control 2
Using the TEST/T-RUN terminals
T-RUN : Test run (compressor and fan motor turn ON).
TEST/MV : Compresses time to 1/60th (accelerates
operation by 60 times faster than normal).
TEST/T-RUN terminals
(TEST)/MV
T-RUN COM