9. TROUBLESHOOTING
9-1. Check before and after troubleshooting
9-1-1. Check power supply wiring
Check that power supply wires are correctly connected to terminals No. 5 and No. 6 on the terminal plate
in the outdoor unit.
Hazardous voltage can cause ELECTRIC SHOCK or
DEATH. Disconnect power or turn off circuit break-
er before you start checking or servicing.
WARNING
INDOOR
INDOOR UNIT
Terminal
Disconnect
switch
(Field supply)
1
2
3
1
2
3
4
5
6
GG
Grounding
line
Power supply line
C0951, CL0951.......1-phase, 115 V
C1251, CL1251.......1-phase, 115 V
C1852, CL1852.......1-phase, 230/208 V
(Inter-unit)
Power lines
Terminal
OUTDOOR UNIT
Fuse
L1
L2
9-1-2. Check inter-unit wiring
Check that inter-unit wiring is correctly connected to the indoor unit from the outdoor unit.
9-1-3. Check power supply
Check that voltage is in specified range (±10% of the rating).
Check that power is being supplied.
9-1-4. Check lead wires and connectors in indoor and outdoor units
Check that coating of lead wires is not damaged.
Check that lead wires and connectors are firmly connected.
Check that wiring is correct.