62
12-6-7. Combustion Blower Motor Abnormal Revolution
Failure Display on Outdoor Unit PCB:
Check combustion blower motor.
Measure AC voltage at blower motor connector (CN05) (under heating operation, during combustion).
In case of abnormality Replace outdoor unit PCB.
In case of abnormality Replace combustion blower motor.
Disconnect combustion blower motor connector, and measure resistance at connector.
*Use a circuit tester (set to AC range).
*Use a circuit tester (set to range).
Normal PUR – PUR AC 30 – 115 V
*Use a circuit tester (set to AC range).
Normal BLK – BLK AC 104 – 126 V
*Use a circuit tester (set to AC range).
Normal BLK – BLK AC 104 – 125 V
Normal BLK – BLK 300 – 500
Normal BLK – BLK 300 – 500
Normal PUR – PUR 10 – 30
12-6-8. ON/OFF Valve Failure
Failure Display on Outdoor Unit PCB: ● ●
Check ON/OFF valve coil (CN06).
Measure AC voltage at the ON/OFF valve coil connector (under heating operation, during combustion).
In case of abnormality Replace outdoor unit PCB.
In case of abnormality Replace ON/OFF valve coil.
Disconnect ON/OFF valve connector and measure resistance at connector.
*Use a circuit tester (set to range).
12-6-9. Reversing Valve Failure
Failure Display on Outdoor Unit PCB: ● ●
Check reversing valve coil.
Measure AC voltage at reversing valve coil connector (CN03) (under heating operation, during combustion).
In case of abnormality Replace outdoor unit PCB.
In case of abnormality Replace reversing valve coil.
Disconnect reversing valve coil connector and measure resistance at connector.
Caution: Reversing valve failure can be displayed when there is a shortage of refrigerant. Therefore if the
above check shows normal, check the amount of refrigerant.
*Use a circuit tester (set to range).