Samsung US12AA(AB)MC Air Conditioner User Manual


 
E-38
INSTALLING THE OUTDOOR UNIT
Auxiliary Circuit Breaker
Electrical Work
1 The supply voltage must be the same as the rated voltage of the
air conditioner.
2 Prepare the power souce for exclusive use with the air conditioner.
3 Use 15 amperes time delay fuse or circuit breaker.
When using the special NFB, use the NFB to bear the capacity of the
air conditioner.
Otherwise, the shot circuit in the NFB may occur.
Outdoor unit
Distribution
board
Auxiliary
power s/w
Auxiliary circuit breaker should be installed near outdoor unit so
that each access is possible. Main/outdoor power supply cable are
connected to upper/lower terminal of auxiliary circuit breaker.
It is necessary that the conduit kit for power supply to the outdoor
unit be installed between auxiliary power S/W and the outdoor
unit. (the conduit kit is optional)
The designs and shape are subject to
change according to the model.
MODEL
AS09A5(A6)MA AS12A5(A6)MC
Power supply
Power cable
Assembly cable
Operating current(C)
Starting Current
Power consumption (C)
115V~/60Hz
Single phase
AS07A5(A6)MA
115V~/60Hz
Single phase
3G AWG 14
4G AWG 16
31A
1320W
47A32A
6.4 8.5 6.1
900W680W
208-230V~/60Hz
Single phase
MODEL
AS18A5(A6)RC
AS18A9(A0)RCD
AS24A1(A2)RC
Power supply
Power cable
Assembly cable
Operating current(C)
Starting Current
Power consumption (C)
208-230V~/60Hz
Single phase
AS12AA(AB)MC
208-230V~/60Hz
Single phase
3G AWG 14
4G AWG 16 5G AWG 16 6G AWG 16
10.5A
10.5A
2350W
35A 37A
8.6A 8.0A
31A
5.4
1900W 1770W1230W
208-230V~/60Hz
Single phase
208-230V~/60Hz
Single phase