E-38
INSTALLING THE OUTDOOR UNIT
Auxiliary Circuit Breaker
Electrical Work
1 The supply voltage must be the same as the rated voltage of the
air conditioner.
2 Prepare the power souce for exclusive use with the air conditioner.
3 Use 15 amperes time delay fuse or circuit breaker.
➢ When using the special NFB, use the NFB to bear the capacity of the
air conditioner.
➢ Otherwise, the shot circuit in the NFB may occur.
Outdoor unit
Distribution
board
Auxiliary
power s/w
◆ Auxiliary circuit breaker should be installed near outdoor unit so
that each access is possible. Main/outdoor power supply cable are
connected to upper/lower terminal of auxiliary circuit breaker.
◆ It is necessary that the conduit kit for power supply to the outdoor
unit be installed between auxiliary power S/W and the outdoor
unit. (the conduit kit is optional)
❊ The designs and shape are subject to
change according to the model.
MODEL
AS09A5(A6)MA AS12A5(A6)MC
Power supply
Power cable
Assembly cable
Operating current(C)
Starting Current
Power consumption (C)
115V~/60Hz
Single phase
AS07A5(A6)MA
115V~/60Hz
Single phase
3G AWG 14
4G AWG 16
31A
1320W
47A32A
6.4 8.5 6.1
900W680W
208-230V~/60Hz
Single phase
MODEL
AS18A5(A6)RC
AS18A9(A0)RCD
AS24A1(A2)RC
Power supply
Power cable
Assembly cable
Operating current(C)
Starting Current
Power consumption (C)
208-230V~/60Hz
Single phase
AS12AA(AB)MC
208-230V~/60Hz
Single phase
3G AWG 14
4G AWG 16 5G AWG 16 6G AWG 16
10.5A
10.5A
2350W
35A 37A
8.6A 8.0A
31A
5.4
1900W 1770W1230W
208-230V~/60Hz
Single phase
208-230V~/60Hz
Single phase