E-27
ENGLISH
Power
Sub switch
Fuse
Electric wire
Allowable voltage
Single phase 208-230V~, 60Hz
30A
30A
3.5mm
2
5.5mm
2
187V~253V
Below 20m(65
Below 50m(164
ft)
ft)
5
8
1
16
ELECTRICAL WORK
The electrical work should be performed by a specialist qualified for the work.
◆ Use the three phase power supply, and be sure to install the sub power distributing board for
exclusive use with the unit(separately purchased by the user).
❈ Avoid octopus-type wiring as it can cause a drop in voltage, thus resulting in poor performance
of the automatic control circuit.
◆ Be sure to install circuit breaker (separately purchased by the user).
◆ Be sure to connect the grounding wire.
◆ When connecting the wiring harness between the indoor and outdoor unit, align the outdoor side and the
indoor side with the terminal board No.
◆ Connect the connection wire (1, 2, 3) and power cable (L1, L2) to terminals through the conduit hole
as shown in the diagram.
❈ When the wiring harnesses of the indoor and outdoor unit are not properly connected, it may cause trouble.
Be careful not to allow the indoor and outdoor wirings and power lines to get in contact with the service valve
of the refrigerant system or to the pipe without an insulator.
❏
Electric power spec
❏
Indoor and Outdoor Connection Wiring
1. Connect it to the terminal board L1 and L2 for power supply to the outdoor unit.
In so doing, peel off the end of the power cord by about 5mm(
"
), and press the cord to the ring
terminal for hooking.
2. Perform the power grounding using the screw for exclusive use with the outdoor unit.
❏
Electrical Wiring
L1 L2
12345
INDOOR SIDE
Terminal board
OUTDOOR SIDE
Terminal board
Indoor/outdoor unit
connection wire(1mm
2
)
Electric panel board
Earth
Earth
Earth
Electric panel board
Cover terminal
Cover
connector
Holder
clamp
Terminal block
3