Operating advanced function _39
ENGLISH
Booster Heater Variables for Controlling DHW Tank
• The FSV #3031 should be set to “1(On)”(Default) to use booster heater as an additional heat
source for DHW tank.
• Booster heater startup delay timer : In case of DHW request, this timer will delay the
operation of booster heater compared to heat pump.
- FSV #3032(Default 20 min., Range 20 ~ 95 min.), In “Power” DHW mode, the delay timer
will be neglected, and the booster starts immediately.
- In “Economic” DHW mode, the DHW heating will be conducted only with heat pump.
- #3032 should be smaller than the maximum H/P time(#3025). If the delay time is set too
high, it might take very long time for DHW heating.
• Temperature difference determining the booster heater OFF temperature(T_BH OFF = Tu +
#3033) : FSV #3033, Default 0˚C, Range : 0 ~ 4˚C.
- Temperature difference determining the booster heater ON temperature(T_BH ON = T_BH
OFF - 2)
• DHW compensation temperature in case of space heating/cooling priority : FSV #3034 will
be explained in next page.
The FSV #4022 for booster heater priority should be set to “0(both)”(Default) or
“2”(booster) to use booster heater.
If not(backup heater priority), the booster heater can be operated in case of no backup
heater demand.
Disinfection Function
• The FSV #3041 should be set to “1(On)”(Default) to use disinfection function.
- Scheduling : Day(#3042, Default “Friday”), starting time(#3043, Default “23:00”),
target tank temp. (#3044, Default “70˚C”), duration(#3045, Default 10 min.)
Disinfection function can be performed only with Samsung’s DHW tank installation.
Urgent DHW by User’s Input (Hot Key of Wired Remote Controller)
• By default setting(#3061, Default “0(Off)”, Urgent DHW heating will not be turned off
automatically before user’s additional key input. If you want to quit urgent DHW function after
a certain amount of duration time(#3052, Default “60 min.”, Range 30 ~ 300 min.), change
the FSV #3051 to “1(On)”.
Additional Solar Panel Installation for DHW with Heat Pump (Field Option)
• By default setting(#3051, Default “1(Yes)”, the DHW heating by solar panel has a priority over
the heat pump operation in case of solar panel installation.