Samsung AD18B1C09 Air Conditioner User Manual


 
14
3-3-4 When the fan of indoor unit does not operate
1) Inspection items
(1) Is the power voltage normal?
(2) Is the connector of indoor fan with the good contact? (CN73)
(3) Is the soldering status of running condenser (CR71) with the good contact?
(4) Is connector of the Hall IC with the good contact (CN 43) ?
(5) Is the indoor fan rotating when it is under operation mode?
(6) Is the FAN LED (green) flickering when the indoor fan stalled (for more than 15 seconds) and
the trouble condition of speed detecting part?
Put the power off and put it on after 5 seconds.
Replace the indoor unit PCB Ass'y due to the
Micom defect.
If the power is not available
(indoor unit), item no 3-3-1.
Replace of indoor unit PCB Ass'y.
Replace the IC 06 (KID 65003)
and SS71(G3MB202pl).
Replace Q401 (Ksc 945Y).
Replacement of
indoor unit fan motor.
Is the operation lamp flickering for 3 minutes and
then put off?
Is AC 120V and higher shown across the indoor fan
connector (CN73) ?
Is the type of MICOM (IC 04) Pin no.
63 old type ?
120Hz
If the operation /stop button of the remote controller
is pressed, is the operation lamp flickering and then is
the indoor fan rotating after 5~6 seconds?
Error occurs after the
indoor unit fan motor is
rotating for 15 seconds?
(FAN Lamp flickering)
YES
YES
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
Is the pin no. 12 of IC 06 (KID 65003)
the old type?
Is the pin no 25 of MICOM
the old type?
120Hz
DB98_05645A(1)_1 5/30/02 7:04 PM Page 14