Robertshaw 9405 Thermostat User Manual


 
IMPORTANT SAFETY INFORMATION
WARNING:
Always turn off power at main fuse or circuit breaker panel before
installing, removing, cleaning, or servicing thermostat.
Read all the information in this manual before installing this
thermostat.
This is a 24 VAC low-voltage thermostat. Do not install on voltages
higher than 30 VAC.
All wiring must conform to local and national building and electrical
codes and ordinances.
Do not short (jumper) across terminals on the gas valve or at the
system control to test installation. This will damage the thermostat
and void the warranty.
Do not connect ground to any terminal in this unit.
Step 1: Replacing Existing Thermostat
1. Turn off power to heating system.
2. Remove cover from old thermostat to expose wires (Figure 1).
3. Disconnect wires one at a time from existing terminals. Use enclosed labels
to mark existing wires. Refer to cross references in Table 1 if existing wiring
does not directly match the labels.
4. Remove existing thermostat base from wall.
Old Terminal New Label Description
M,R,Rh,R5 or 5 R Heat transformer, hot side
H,W, or 4 W Heating control
F or G G Fan control relay
NOTE: ON SOME OLDER MODELS, THE C TERMINAL CAN BE EITHER THE COOLING CONTROL
OR THE COMMON SIDE OF THE TRANSFORMER. CHECK FURNACE WIRING DIAGRAM
TO VERIFY C TERMINAL. IF IT IS THE COMMON SIDE OF THE TRANSFORMER, CAP
THE WIRE AND TUCK INTO THE WALL.
Table 1
2
Figure 1
!