Roberts Gorden BH30UT/EF Furnace User Manual


 
SECTION 5: GENERAL SUSPENSION DETAILS
11 of 75
SECTION 5: GENERAL SUSPENSION DETAILS
To e nsure your safety, and comply with the terms of the
warranty, all units must be installed in accordance with
these instructions.
The gas or the electrical supply lines must not be used to
support the heater.
Do not locate the gas or electric supply lines directly over
the path of the flue products from the heater.
The heater must be installed in a location that it is readily
accessible for servicing.
The heater must be installed in accordance with
clearances to combustibles as indicated in this manual.
The minimum and maximum gas inlet pressures must be
maintained as indicated on the rating plate. Typical
installation configu rations are shown on Page 12, Figure
18.
Note: Some modles will receive S-hooks (P/N 91907302)
or spring hooks (P/N 91903300), rather than bow
shackles.
WARNING
Severe Injury Hazard
Secure burner to burner tube with bolts and
lockwashers.
Hang heater with materials with a minimum
working load of 75 lbs (33 kg).
Failure to follow these instructions can result
in death, injury or property damage.
WARNING
Cut/Pinch Hazard
Wear protective gear during installation,
operation and service.
Edges are sharp.
Failure to follow these instructions can result
in injury.