7
102961
WARNING
Review and understand the warnings in the
Safety
Information Section
, page 3. They are needed to safely
operate this heater. Follow all local codes when using this
heater.
OPERATION
To Start Heater
1. Follow all ventilation and safety information.
2. Fill fuel tank with kerosene.
3. Attach fuel cap.
4. Plug power cord into grounded receptacle with 100 Volts, 50 or 60 Hz.
5. Turn ON/OFF switch to "ON".
Extension Cord Wire Size Requirements
Up to 100 feet (30.5 meters) long, use 16 AWG (1.0 mm
2
) conductor
101 to 200 feet (30.6 to 61 meters) long, use 14 AWG (1.5 mm
2
) conductor
If heater does not start, push in flame-out control reset button (see Figures 5
and 6).
Continued
Figure 5 - Flame-Out Control Reset
Button (REMJ70)
Figure 6 - Flame-Out Control Reset
Button (REMJ150)
Flame-Out
Control
Reset
Button
Flame-
Out
Control
Reset
Button
Provide a fresh air opening of at least three square feet (2800 square cm) for each
100,000 Btu/Hr rating. Provide extra fresh air if more heaters are being used.
Example:
A 150,000 Btu/Hr heater requires one of the following:
• a two-car garage door (5 m wide opening) raised 8.6 cm.
• a single-car garage door (2.75 m wide opening) raised 15.3 cm.
• two, 76.2 cm wide windows raised 28 cm.
WARNING
Follow the minimum fresh, outside air ventilation
requirements. If proper fresh, outside air ventilation is not
provided, carbon monoxide poisoning can occur. Provide
proper fresh, outside air ventilation before running heater.
VENTILATION