P36 - P36D Zero Clearance Direct Vent Gas Fireplace
Model P36-NG4 P36-LP4 P36D-NG1 P36D-LP1
Fuel Type Natural Gas Propane Natural Gas Propane
Minimum Supply
Pressure
5” W.C.
(1.25 kPa)
12” W.C.
(3.00 kPa)
5” W.C.
(1.25 kPa)
12” W.C.
(3.00 kPa)
Manifold
Pressure - High
3.8” W.C.
(0.95 kPa)
11” W.C.
(2.74 kPa)
3.8” W.C.
(0.95 kPa)
11” W.C.
(2.74 kPa)
Manifold
Pressure - Low
1.1” W.C.
(0.27 kPa)
2.9” W.C.
(0.72 kPa)
1.1” W.C.
(0.27 kPa)
2.9” W.C.
(0.72 kPa)
Orifi ce Size #37 DMS #52 DMS #37 DMS #52 DMS
Minimum Input
15,500 BTU/h
(4.54 kW)
15,000 BTU/h
(3.96 kW)
15,500 BTU/h
(4.54 kW)
15,000 BTU/h
(3.96 kW)
Maximum Input
30,000 BTU/h
(8.79 kW)
30,000 BTU/h
(8.79 kW)
30,000 BTU/h
(8.79 kW)
30,000 BTU/h
(8.79 kW)
Vent Sizing
4” Inner / 6 5/8”
Outer
4” Inner / 6 5/8”
Outer
4” Inner / 6 5/8”
Outer
4” Inner / 6 5/8”
Outer
A
D
C
F
E
A
B
Unit Dimensions Description P36 P36D
A Front Face Width 36” (914mm) 36” (914mm)
B Rear Firebox Width 33-1/4” (838mm) 33-1/4” (838mm)
C Front Face Height 30-1/2” (775mm) 30-1/2” (775mm)
D Height w/ Standoff 36” (914mm) 37” (940mm)
E Unit Depth 12-3/4” (324mm) 17-1/8” (435mm)
F Height to Vent 32-1/2” (826mm) 32-1/2” (826mm)
Framing Dimensions Description P36 P36D
G Framing Width* 36-1/4” (921mm) 36-1/4” (921mm)
H*** Framing Height* *** 36-1/4” (921mm)*** 37-1/4” (946mm)***
I Framing Depth* 12-3/4” (324mm) 17-1/8” (435mm)
J Corner Wall Length 42-7/16” (1078mm) 48” (1219mm)
K
Corner Facing Wall
Width
60” (1524mm) 68” (1727mm)
L Framed Chase Ceiling 46” (1168mm) 46-1/2” (1181mm)
M Vent Centerline Height 40-1/2” (1029mm) 40-1/2” (1029mm)
N Gas Connection Height 2” (51mm) 2” (51mm)
O Gas Connection Inset 3-1/2” (89mm) 3-1/2” (89mm)
P Gas Connection Width 4” (102mm) 4” (102mm)
G
H
I
K
J
L
O
P
N
M
10" (254mm)
dia. Hole through
wall Vent.
Opening for gas
connection
Top Header
Drywall
(or other
facing)
*
If using the Barcelona Surround, Kensington, Balmoral, or
Tripoli Screen Door please note that framing and facing must
be non combustible (12” on top and 6” on both sides) and that
the Barcelona is only approved for installation with a single
sidewall.
P36 - P36D Gas Fireplace
Approved Venting Systems
Flex Vent Systems: FPI AstroCap™ Flex Vent
Rigid Pipe Vent Systems: Simpson Dura-Vent® Direct Vent GS
American Metal Products Ameri Vent
Security Secure Vent®
Selkirk Direct-Temp.
***
Important: Framing height requires consideration of the hearth
depth. Dimension H = H + the thickness of installed hearth.
Please refer to Page 11 (Exterior Vent Terminations)
for additional guidelines on vent locations.
35June 2007 Regency Product Specifi cations Book
Gas Fireplaces