Regency L234 Indoor Fireplace User Manual


 
Faceplate
Combustible
Flooring
Mantel
C
12" Max.
D
Top of
Door Frame
Faceplate
12” Min.
Hearth
Mantel
C
12" Max.
D
Existing or
Non-Combustible Hearth
Top of
Door Frame
4” min
G
Clearances
Unless otherwise stated the clearances listed below are Minimum
distances to combustible materials. Please Note: A major cause
of chimney related fi res is due to a failure to maintain required
clearances (air space) to combustible materials. It is of the greatest
importance that this fi replace and vent system be installed only in
accordance with these instructions.
Combustible Mantels
Because of the extreme heat this fi replace emits, the mantel
clearances are critical. Combustible mantel clearances from top of
the louvers are shown in the diagram below. Mantel may be installed
anywhere in the shaded area or higher.
Note: A non-combustible mantel may be installed at a lower
height.
Note: Ensure the paint that is used on the mantel and the facing
is “heat resistant” or the paint may discolour.
Clearances to Combustibles
Dimension Description L234
A From Unit to Side Walls 8” (203mm)
B From Unit to Ceiling 56” (1422mm)
C Minimum Mantel Height 21” (533mm)
D Maximum Mantel Depth 12” (305mm)
E Alcove Width 60” (1524mm)
F Alcove Depth 36” (914mm)
G Hearth Height 1-1/2” (38mm)
H Hearth Width 28” (711mm)
I Hearth Depth 12” (305mm)
Dimensions are measured from the edge of the door frame.
Flush Front Mantel Clearances
L234 Gas Insert
Hearth Clearances Flush and Raised
No Hearth required when unit is raised 4”
124 June 2007 Regency Product Specifi cations Book