Regency E33S Indoor Fireplace User Manual


 
Clearances
Unless otherwise stated the clearances listed below are Minimum
distances to combustible materials. Please Note: A major cause
of chimney related fires is due to a failure to maintain required
clearances (air space) to combustible materials. It is of the greatest
importance that this fireplace and vent system be installed only in
accordance with these instructions.
Combustible Mantels
Because of the extreme heat this fireplace emits, the mantel
clearances are critical. Mantel may be installed anywhere in the
shaded area or higher.
Note: A non-combustible mantel may be installed at a lower
height.
Note: Ensure the paint that is used on the mantel and the facing
is “heat resistant” or the paint may discolour.
Clearances to Combustibles
Dimension Description E33S
A* From Unit to Side Walls 8” (203mm)
B From Unit to Ceiling 47” (1194mm)
C Minimum Mantel Height 15” (381mm)
D Maximum Mantel Depth 3-1/2” (89mm)
E Alcove Width 76” (1930mm)
F Alcove Depth 36” (914mm)
* Alcove side wall must have a minimum of 8” (203mm) clearance on one side.
Regency E33 Sunrise Gas Insert
E33S Sunrise Gas Insert