Regency C34 Indoor Fireplace User Manual


 
C34 Freestanding Direct Vent Gas Stove
Gas Line In
J
C
I
H
Gas Line In
A
B
D
F
G
E
K K
L
Back wall
Wall
Side wall
Side wall
Wall
N
M
P
P
O
O
Model C34-NG3 C34-LP3
Fuel Type Natural Gas Propane
Minimum Supply Pressure 5.0” W.C. (1.25 kPa) 12.0” W.C. (3.00 kPa)
Manifold Pressure - High 3.82” W.C. (0.95 kPa) 11” W.C. (2.74 kPa)
Manifold Pressure - Low 1.1” W.C. (0.27 kPa) 2.9” W.C. (0.72 kPa)
Orifi ce Size #36 #52
Minimum Input 16,000 BTU/h 16,000 BTU/h
Maximum Input 32,000 BTU/h 32,000 BTU/h
Vent Sizing 4” Inner / 6-5/8” Outer 4” Inner / 6-5/8” Outer
C34 Gas Stove
Dimension Description C34
A Unit Width 24” (610mm)
B Unit Height 29-11/16” (737mm)
C Unit Depth 21-5/8” (549mm)
D Pedestal Height 11-3/4” (298mm)
E Cast Leg Height
(including Bottom shield) 11-3/4” (298mm)
F Bottom shield Height 4” (102mm)
G Vent centerline to Side 12” (305mm)
H Vent centerline to Back 7” (178mm)
I Gas Line Height (from base) 9” (229mm)
J Side to Gas Line 4-1/2” (114mm)
Alcove clearances
Dimension Description C34
K Side Wall to Unit 10” (250mm)
L Back Wall to Unit 6” (150mm)
M Side wall to Vent Centerline 22” (559mm)
N Back wall to Vent Centerline 13” (330mm)
Corner Clearances
Dimension Description C34
O Wall to Unit Corner 1.5” (38mm)
P Wall to vent centerline 14” (356mm)
Minimum ceiling height is 36" (914mm) from top of unit.
Minimum clearance to vent is 1-1/4” (32mm).
The above listed clearances are minimum distances to combustible
materials. When installing on carpet or vinyl fl ooring the bottom pedestal
cover plate must be installed.
Approved Venting Systems
Flex Vent Systems: FPI AstroCap™ Flex Vent
Rigid Pipe Vent Systems: Simpson Dura-Vent® Direct Vent GS
American Metal Products Ameri Vent
Security Secure Vent®
Selkirk Direct-Temp.
145June 2007 Regency Product Specifi cations Book