Raypak Raytherm 4001 Water Heater User Manual


 
Catalog No.: 1000.96B Effective: 11-15-07 Replaces: 10-15-01
Power Vent
For Raytherm 2100 - 4001 Model
Max. Runt (ft.) Dimensions Electrical Ratings
Raytherm
Model
MBTU
Vert. Horiz. A B C E F K Volts Amps HP
Max. CFM
@ 70°F
2100 2100 20 60 16-7/8 22-3/8 33-1/2 17-1/4 7-11/16 14 115 7.2 1/2 1900
2500 2499 20 60 16-7/8 22-3/8 33-1/2 21-3/4 12-3/16 14 115 7.2 1/2 1900
3001 3000 20 60 24-1/4 27-3/8 44-3/4 23-5/8 10-1/8 16 115 10.7 3/4 3400
3500 3500 20 60 24-1/4 27-3/8 44-3/4 29-1/4 15-3/4 16 115 10.7 3/4 3400
4001 4000 20 60 24-1/4 27-3/8 44-3/4 34-7/8 21-3/8 18 115 10.7 3/4 3400
Notes: 1. Vent pipe sizes are based on standard horizontal discharge with maximum sixty feet of horizontal length with
no elbows, 300°F nominal flue temperature, and sea-level operation. (Allow 10 ft. equivalent length
adjustment for each 90° elbow.) For installation under other conditions, please consult the factory.
2. Left discharge is standard.
3. Vent pipe must meet Category III appliance venting requirements.
4. Follow installation instructions provided by power vent manufacturer.