Raypak 504 thru 2004 Water Heater User Manual


 
Simple Serviceability
Raypak’s easy-to-understand user interface, including on-board diagnostics and LED operating status lights, tells the technician all he needs to
know. All service/repair components are readily accessible from the front or side for maximum installation flexibility. To enhance serviceability,
the control box is completely removable allowing total access.
LED status panel
Ignition control
Burner on/off
Pump on/off
MVB Control Panel
Service diagnostic panel
CATEGORY I*
BOILERS
(TYPE H)
MVB
Model
Flow Rates Pressure Drops
Minimum Flow Maximum Flow 20°F 30°F 40°F
GPM
P FT T °F
GPM
P FT T °F
GPM
P FT
GPM
P FT
GPM
P FT
504 25 1.1 34 100 11.3 8 42 2.7 28 1.4 N/A N/A
754 32 1.7 40 100 13.8 13 63 6.0 42 2.9 32 1.7
1104 46 4.1 40 113 18.6 16 92 13.3 62 6.7 46 4.1
1504 63 8.0 40 113 22.2 22 N/A N/A 84 13.3 63 8.0
2004 84 16.0 40 113 27.2 30 N/A N/A 112 26.9 84 16.0
CATEGORY I*
WATER HEATERS
(TYPE WH)
MVB
Model
Flow Rates Pressure Drops
Minimum Flow Maximum Flow 20°F 30°F
GPM
P FT T °F
GPM
P FT T °F
GPM
P FT
GPM
P FT
504 50 2.8 17 100 11.3 8 N/A N/A 28 1.4
754 50 3.5 25 100 13.8 13 64 6.1 42 3.0
1104 60 6.3 30 113 18.6 16 90 12.6 60 6.3
1504 82 12.6 30 113 22.2 22 N/A N/A 82 12.6
2004 109 25.5 30 113 27.2 29 N/A N/A 109 25.5
CATEGORY IV BOILERS
& WATER HEATERS
(TYPE H & WH)
MVB
Model
Flow Rates Pressure Drops
Minimum Flow Maximum Flow 20°F 30°F 40°F
GPM
P FT T °F
GPM
P FT T °F
GPM
P FT
GPM
P FT
GPM
P FT
503 25 1.1 35 100 11.3 9 43 2.8 29 1.4 N/A N/A
753 33 1.9 40 100 13.8 13 65 6.4 43 3.1 33 1.9
1003
43
3.7 40 113 18.6 15 87 12.0 58 6.0 43 3.7
1253
54
6.2 40 113 22.2 19 109 20.9 73 10.2 54 6.2
1503
65
9.5 40 113 25.5 23 N/A N/A 87 16.0 65 9.5
1753
76
13.4 40 113 27.2 27 N/A N/A 101 22.5 76 13.4
2003
87
15.2 40 116 30.2 30 N/A N/A 116 31.9 87 18.9
6
*Category I with vertical vent, category III with horizontal venting and no extractor.
† Minimum flow 50GPM for WH hot water supply.
‡ Use 30° column as minimum flow for hot water supply.
Boiler Only