Catalog No.: 2000.61C Effective: 12-01-10 Replaces: 07-10-09
XTherm – Type H
Models 1005-2005 Model
Dimensions (in)
MBTUH
Model
(H7-)
Input Output
B
Height
D E F
G*
NPT
K
Flue
Ø
L M
N
C/A
Ø
P R Y
Ship
Weight
(Lbs.)
1005 999 959 55-1/8 45 47-1/8 36-1/2 1-1/4 6 40-1/16 11-1/2 6 47-1/8 8-1/16 6-1/16 1065
1505 1500 1440 67-1/8 57 59-1/16 38-1/2 1-1/4 8 52-1/16 12-5/8 8 59-1/8 8-3/16 6-1/16 1234
2005 1999 1919 81-1/8 71 71-3/16 38-1/2 2 8 64-1/16 12-5/8 8 73-1/8 8-3/16 6-1/4 1461
Note: Ratings shown are for elevations up to 4,500 feet. For installations at elevations
above 4,500 feet, please consult the factory for additional instructions.
* For Propane Gas, all models are 1” NPT
Model 1005 Model 1505 Model 2005
Minimum Pipe Size
2
Minimum Pipe Size
2
Minimum Pipe Size
2
System
Return
Temp
(ºF)
Supply
Temp
1
(ºF)
<80’ eq 80-200’ eq
Supply
Temp
1
(ºF)
<80’ eq 80-200’ eq
Supply
Temp
1
(ºF)
<80’ eq 80-200’ eq
60 138 2” NPT 2-1/2” NPT 147 2” NPT 2-1/2” NPT 154 2” NPT 2-1/2” NPT
80 138 2” NPT 2-1/2” NPT 147 2” NPT 2-1/2” NPT 154 2-1/2” NPT 3” NPT
100 138 2-1/2” NPT 3” NPT 147 2-1/2” NPT 3” NPT 154 2-1/2” NPT 3” NPT
120 145 2-1/2” NPT 3” NPT 158 2-1/2” NPT 3” NPT 170 2-1/2” NPT 3” NPT
140 165 2-1/2” NPT 3” NPT 178 2-1/2” NPT 3” NPT 190 2-1/2” NPT 3” NPT
160 185 2-1/2” NPT 3” NPT 198 2-1/2” NPT 3” NPT 210 2-1/2” NPT 3” NPT
1
– Approximate high fire heater outlet temperature based on the standard heater pump and recommended connecting pipe size.
2
– Minimum pipe size based on total equivalent feet of supply and return piping between the system loop and heater.
NOTE
:
Primary/Secondary plumbing
is mandatory for proper operation.
CLEARANCES
(in.)
Front Rear Right Left Top Floor Vent
Certified Minimum 24 12 1 1 0 0 1
Minimum Service 24 36 24 1 10 N/A N/A
Amp Draw**
Model
Boiler † Accessories †
1005 12** 10
1505 12** 14
2005 18** 17
† Separate power connections are
factory supplied and separate supply
breakers must be field supplied.
** Current draw is for boiler only (Supply
breaker must have delayed trip).