Raypak 1005-2005 Boiler User Manual


 
Catalog No.: 2000.61A Effective: 9-15-08 Replaces: 7-1-08
XTherm – Type H
Models 1005-2005 Model
Dimensions (in.)
Model
(H7-)
MBTUH
B D E F G* K L M N P R Y
Ship
Weight
(Lbs.)
Total
Amps**
Input Output Height NPT Flue Ø C/A Ø
1005 999 959 55-1/8 45 47-1/8 36-1/2 1-1/4 6 40-1/16 11-1/2 6 47-1/8 8-1/16 6-1/16 1065 22
1505 1500 1440 67-1/8 57 59-1/16 38-1/2 1-1/4 8 52-1/16 12-5/8 8 59-1/8 8-3/16 6-1/16 1234 26
2005 1999 1919 81-1/8 71 71-3/16 38-1/2 2 8 64-1/16 12-5/8 8 73-1/8 8-3/16 6-1/4 1461 35
Note: Ratings shown are for elevations up to 4,500 feet. For installations at elevations
above 4,500 feet, please consult the factory for additional instructions.
* For Propane Gas, all models are 1
** Supply breaker must have delayed trip.
Rate of Flow (GPM) Maximum Flow Minimum Flow*
Model
(H7-)
20°F T 30°F T
40°F
T*
GPM
T (°F)
GPM
T (°F)
1005 95 63 47 113 17 47 40
1505 N/A 96 71 113 25 71 40
2005 N/A N/A 95 116 33 95 40
* Closed systems only
NOTE: Primary/Secondary plumbing
is mandatory for proper operation.
CLEARANCES (in.)
Front Rear Right Left Top Floor Vent
Certified Minimum 24 12 1 1 0 0 1
Recomm. Service 24 36 24 1 10 n/a n/a