PVI Industries PV500-43 Water Heater User Manual


 
PV500-43
PVIIndustries,LLCP.O.Box7124Ft.Worth,TX7611118004335654Page | 7 7/10
IfPWRLEDdoesnotcomeonandLAandLBdon’tflash,calloremailProtoCessorsupport
support@ProtoCessor.com.
IfPWRLEDdoesnotcomeonbuttheLAandLBflash,thenthePWRLEDisbr oken.
IfLAandLBdon’tstarttoflashtherecould
beaproblemwiththeProtoCessorandyouneedto
contactsupport@ProtoCessor.com.
IfGP105nevercomesonthenyouneedtocontactProtoCessorsupport.
IfTXandorRXdon’tflash,itmayrepresentaproblemwiththefieldwiringorConfiguration
problemsintheProtoCessoronfield
sideorincorrectpollingparameters(suchasCOMM
propertieslikebaud,parity,andetc).
TheGatewayisunabletofindoneormorecontrolsintheRS485network.Theindividual
controlsmaynotbeprogrammedwiththecorrectanduniquenodeaddress.Seetherespective
controlmanualfordetails.
TheGatewayhasnocomm unicationwiththecontrolsintheRS485network.ChecktheRS485
wiringforcorrectwiringmethod.Seepage2ofthismanual fordetails.
MoreinformationfortheProtoCessor/ProtoNodecanbefoundat:Web:www.protocessor.com
FieldServerTechnologies,1991TarobCourt,Milpitas,California95035
USA
Tel:4089644433,FAX:4082629042,TollFree:8003178319Email:sales@protocessor.c o m
TROUBLESHOOTING TIP
S